Phase Academy Interactive Power Systems Lab

Transformer Winding Resistance

NETA · IEEE C57.152
Labs · Transformers · Winding Resistance

Transformer Winding Resistance Test Report

Record, analyze, and trend DC winding-resistance measurements with phase-balance deviation, temperature correction, and NETA-style acceptance guidelines.

NETA ATS-2025 NETA MTS-2023 IEEE C57.152 Temp correction · 234.5 Cu / 225 Al 1–33 tap positions Field / Professional
For education & field documentation only · Verify against codes Documentation aid — not a compliance certification. Thresholds shown are configurable guidelines, not automatic pass/fail rulings. Record the applicable standard edition (e.g. ANSI/NETA ATS-2025 acceptance, ANSI/NETA MTS-2023 maintenance, IEEE C57.152 diagnostic guidance) and the manufacturer/project criteria. Manufacturer/project criteria govern final acceptance.

Correction: Rs = Rm × ((Ts + Tk) / (Tm + Tk)), with Tk = 234.5°C (copper) or 225°C (aluminum) per IEEE C57 practice. Material is taken from the Nameplate section. Use the same reference temperature for every comparison in the record — correction is applied to prior/factory trend comparisons when both measurement temperatures are available.

Guidance: DC test current is generally kept above 1% of the rated winding current for a stable, low-noise reading and at or below 15% of rated so the test current itself does not heat the winding and shift the measurement (IEEE C57 practice). Allow the current to fully stabilize before recording, and demagnetize the core afterward so a subsequent excitation-current, ratio, or differential-relay energization is not affected by residual magnetism. Enter rated currents in the Nameplate section to enable validation.