Record, analyze, and trend DC winding-resistance measurements with phase-balance deviation, temperature correction, and NETA-style acceptance guidelines.
Correction: Rs = Rm × ((Ts + Tk) / (Tm + Tk)), with Tk = 234.5°C (copper) or 225°C (aluminum) per IEEE C57 practice. Material is taken from the Nameplate section. Use the same reference temperature for every comparison in the record — correction is applied to prior/factory trend comparisons when both measurement temperatures are available.
Guidance: DC test current is generally kept above 1% of the rated winding current for a stable, low-noise reading and at or below 15% of rated so the test current itself does not heat the winding and shift the measurement (IEEE C57 practice). Allow the current to fully stabilize before recording, and demagnetize the core afterward so a subsequent excitation-current, ratio, or differential-relay energization is not affected by residual magnetism. Enter rated currents in the Nameplate section to enable validation.