Educational simulator — not an engineering tool. Relay curves are an educational implementation of IEC 60255-151-style IDMT equation constants only. This is not full IEC 60255-151 product compliance, not IEEE/ANSI C37.112, not NEC / NFPA 70 selective-coordination compliance, and not manufacturer minimum-melt / total-clearing data. Real coordination requires actual device curves/bands, a fault-current study, and qualified engineering / AHJ review.
Selected Fault Status
COORDINATED
Global Study Range Status
GLOBAL: COORDINATED ACROSS STUDY RANGE
Fault Current
10.0 kA
Phase fault
Selected-Point Status
--
At fault cursor
DS Clearing Time
--
Downstream
US Clearing Time
--
Upstream
Time Margin
--
CTI target 0.30 s
Trip Order
--
At selected point
🔍 Global Study-Range Scan
Scanning...
📋 Selected-Point Trip Data
Device
Family / model
Result
Clearing time
Element
Downstream Relay
FamilyRelay
ModelIEC IDMT Relay
Pickup400 A
TMS0.20
Phase Inst.5000 A
GF Pickup200 A
GF Inst.OFF
CurveIEC Std/Normal Inverse
Upstream Relay
FamilyRelay
ModelIEC IDMT Relay
Pickup800 A
TMS0.50
Phase Inst.12000 A
GF Pickup400 A
GF Inst.OFF
CurveIEC Std/Normal Inverse
⚡ One-Line Context
💡 Notes & Recommendations
Adjust settings to see recommendations.
📜 Event Log
Relay/breaker curves are an educational implementation of IEC 60255-151-style IDMT equation constants; fuse curves are a generic approximation. These are not manufacturer-specific trip curves/bands, and not IEEE C37.112 or code-compliance data.
🔍 Cursor Info
Hover or click on the TCC plot to see trip times at a specific fault current.
COORDINATED
⏱ Trip Sequence Timeline
📊 Detailed Trip Data
📜 Event Log
🎯 Preset Scenarios
Click a scenario to load a preconfigured protection scheme. Study the TCC curves and coordination status for each.
🎓 Challenge Prompts
Challenge 1: Make the feeder (downstream) trip before the main (upstream) at 8 kA with at least 0.3 s margin.
Challenge 2: Configure a fuse-breaker scheme where the fuse clears low-level faults but the relay trips first above 6 kA.
Challenge 3: Create a marginally-coordinated system that loses selectivity above 15 kA.
Challenge 4: Set the upstream relay so its instantaneous element coordinates with the downstream device clearing time at maximum fault current.
Challenge 5: Coordinate two relays on different curve families (e.g., IEC Normal Inverse downstream, IEC Extremely Inverse upstream).
What Is a TCC (Time-Current Characteristic)?
A TCC curve plots the operating time of a protective device against the fault current magnitude. The horizontal axis is current (log scale) and the vertical axis is time (log scale). Every overcurrent device -- fuse, breaker, or relay -- has a characteristic curve that describes how fast it operates for a given current level.
Pickup Current
The pickup is the minimum current at which a protective device begins to respond. Below pickup, the device ignores the current entirely. For relays, pickup is set by adjusting the current tap. For fuses, it is determined by the fuse rating. For thermal-magnetic breakers, the thermal element sets the pickup threshold.
Pickup must be set above maximum expected load current
Pickup must be below minimum expected fault current for proper detection
Typical rule: pickup = 1.25 to 1.5 x full load current
In NEC-governed installations the overcurrent device rating is also bounded by conductor ampacity and the applicable protection article (for example NEC 240.4 for conductors, 430 Part IV for motor branch-circuit short-circuit and ground-fault protection) -- a coordination-driven pickup never overrides those limits
Time Multiplier Setting (TMS)
The TMS (IEC terminology; IEEE uses "Time Dial Setting" or TDS) shifts the entire inverse-time curve up or down on the time axis. A higher TMS means the device takes longer to trip at any given fault current. This is the primary knob for coordination -- you set the downstream device faster (lower TMS) and the upstream device slower (higher TMS) so that the downstream device always clears the fault first.
Lower TMS = faster operation
Higher TMS = slower operation
The CTI (Coordination Time Interval) between upstream and downstream should be at least 0.2-0.4 seconds
IEC typical range: 0.05 to 1.0 (this tool extends to 1.2 for demonstration)
Slowing an upstream device to gain margin must still respect equipment damage curves and, where applicable, the arc-energy-reduction requirements of NEC 240.87
Instantaneous Element
The instantaneous pickup overrides the time-delay curve. When fault current exceeds this threshold, the device trips with no intentional delay (typically 1-3 cycles, or 0.016-0.05 seconds). Instantaneous elements provide fast clearing of high-magnitude faults but can cause coordination problems if set too low.
Set above the maximum fault current seen by the downstream device, if coordination is required
Provides fast clearing for close-in faults
May need to be disabled on some relay applications for coordination
Disabling instantaneous protection to buy selectivity increases incident energy; NEC 240.87 requires a documented arc-energy-reduction method for circuit breakers rated or adjustable to 1200 A and above
Ground Fault Protection
Ground fault relays detect current flowing to ground through a separate CT circuit. Their pickup is typically set much lower than phase overcurrent because ground faults often produce less current than three-phase faults, but must still be detected and cleared promptly. Use the Phase/Ground fault type selector to switch the analysis mode.
Equipment protection (GFPE): NEC 230.95 requires ground-fault protection on solidly grounded wye services over 150 V to ground and 1000 A or more, with a maximum setting of 1200 A and a maximum time delay of one second for ground-fault currents of 3000 A or more. Similar requirements appear in 215.10 (feeders) and 240.13 (building disconnects).
Personnel protection is a different device: a Class A GFCI trips at 4-6 milliamps (UL 943). No breaker or relay ground-fault setting in this tool is shock protection for people.
Coordinating two GFPE devices in series generally requires a zone-selective interlock or a deliberate time step, because both may be set near the same low pickup.
IEC 60255 IDMT Curve Families
This tool implements IEC-style Inverse Definite Minimum Time (IDMT) equations. These are not IEEE/ANSI C37.112 curves.
IEC Standard / Normal Inverse: t = TMS × 0.14 / (M0.02 - 1). Moderate slope; general purpose.
IEC Very Inverse: t = TMS × 13.5 / (M - 1). Steeper slope; better for feeders with high variation in fault current.
IEC Extremely Inverse: t = TMS × 80 / (M2 - 1). Very steep; good for coordination with fuses.
Definite Time: Fixed time delay (entered directly in seconds) regardless of current above pickup.
Where M = I/Ipickup (multiple of pickup current)
Coordination Principles
The device closest to the fault should trip first (downstream before upstream)
Maintain a Coordination Time Interval (CTI) of at least 0.2-0.4 s between curves
Check coordination across the entire range of possible fault currents, not just one point
Instantaneous elements can break coordination at high current levels
Fuse-breaker coordination requires careful curve comparison using manufacturer data
Where the NEC mandates selective coordination -- elevators (620.62), emergency systems (700.32), legally required standby (701.32), critical operations power (708.54) -- the requirement is full selectivity over the fault range and time, verified with manufacturer data, not a curve-shape approximation like this one
Common Mistakes
Setting downstream pickup higher than upstream pickup -- removes selectivity
Ignoring the instantaneous region -- curves may cross at high currents
Insufficient CTI -- relay overtravel, breaker clearing time not accounted for
Not checking coordination at both minimum and maximum fault levels
Using the same curve family on both devices when different families would coordinate better
Forgetting motor inrush or transformer energization when setting pickups
Relying on single-point checks instead of full curve comparison
Treating a generic curve equation as a substitute for manufacturer minimum-melt / total-clearing bands or a listed fuse-breaker series-rating combination
Motor & Transformer Inrush
Motor inrush: When a motor starts, it draws 5-7x its full load current for several seconds. Protection devices must not trip during normal motor starting. The inrush point is typically plotted at 6x FLA for 5-10 seconds.
Transformer inrush: Energizing a transformer produces inrush current of 8-12x rated current that decays over 0.1-0.5 seconds. The relay must ride through this transient without false tripping.
Riding through inrush is a floor, not a license: motor branch-circuit protection is still bounded by NEC Table 430.52 and transformer primary/secondary protection by NEC 450.3.
Quiz Score: 0 / 10 -- Answer all questions below
Quiz 1: Pickup Fundamentals
A relay has a pickup setting of 600 A. A fault produces 450 A. What does the relay do?
The relay only begins timing when current exceeds the pickup threshold (600 A). At 450 A the relay sees this as normal load or a fault too small to act on.
Quiz 2: Time Multiplier Setting
Increasing the TMS on an inverse-time relay will:
TMS is a multiplier on the time axis. A higher TMS shifts the entire curve upward (slower). The pickup current and curve shape are not affected by TMS.
Quiz 3: Coordination Time Interval
What is the typical minimum Coordination Time Interval (CTI) between upstream and downstream devices?
The CTI accounts for breaker clearing time, relay overtravel, and safety margin. Industry practice is 0.2 to 0.4 seconds (often 0.3 s is used as default).
Quiz 4: Selectivity
For proper selectivity, which device should trip first for a fault on the load side?
Selectivity means only the device nearest the fault operates, isolating the smallest portion of the system. The downstream device should always clear the fault first, giving the upstream device time to reset.
Quiz 5: Instantaneous Element
A relay's instantaneous element is set at 8000 A. A 12 kA fault occurs. The relay will:
When fault current exceeds the instantaneous pickup, the relay bypasses the time-delay curve and trips in approximately 0.016 to 0.05 seconds (1-3 cycles at 60 Hz).
Quiz 6: Curve Families
Which IEC curve family provides the steepest time-current slope, making it well-suited for coordination with fuses?
Extremely Inverse curves (t = TMS x 80 / (M^2 - 1)) have the steepest slope. This closely matches the shape of fuse curves, making EI relays ideal for fuse-relay coordination.
Quiz 7: Motor Inrush
A motor draws 6x its full load current during starting. How should the protection be set?
The protection curve must be plotted above and to the right of the motor starting point. If the TCC curve passes through or below the inrush point, the relay will nuisance-trip during normal motor starting. The upper bound on that setting still comes from NEC Table 430.52, not from inrush alone.
Quiz 8: Overlap Problem
You discover that the upstream device trips before the downstream device at 10 kA. What is the most direct fix?
To restore selectivity, make the upstream device slower (increase its TMS) or the downstream device faster (decrease its TMS). This opens up the time margin between the two curves.
Quiz 9: Fuse Behavior
Unlike relays, a fuse:
A fuse melts its element to clear the fault. Once blown, it must be physically replaced. Relays and breakers can be reset and re-closed without replacement.
Quiz 10: Ground Fault Pickup
Why is the ground fault pickup typically set much lower than the phase overcurrent pickup?
Ground faults (especially arcing faults) are often limited by fault impedance and produce much less current than bolted three-phase faults. A lower pickup ensures reliable detection of these lower-magnitude events. For services covered by NEC 230.95 the pickup is also capped at 1200 A with a maximum one-second delay at 3000 A.
Educational Disclaimer: This simulator is for educational and training purposes only. It uses simplified IEC 60255 IDMT formula-based curves for relays and generic approximations for fuses and breakers. Real protective relay coordination requires detailed system studies, actual manufacturer device curves, fault analysis software, and engineering review. Do not use this tool for actual protection system design or selective coordination studies. Always consult qualified protection engineers and use certified coordination software for real installations.