Solidly Grounded
Zero-sequence current has a clear return path through the grounded neutral.
Default assumptions shown here after computation.
System Status: Nominal
Everything is balanced. All three phases carry equal magnitude, 120° apart.
Use the Sequence Sandbox sliders in the sidebar to dial in the three sequence magnitudes and watch them combine into phase quantities. By construction every component here is entered at 0°, so this tab answers “what do in-phase sequence sets add up to?” Real faults give each sequence its own phase angle — see the Fault Explorer tab for solved fault values. Symmetrical components: turning one messy problem into three tidy ones since 1918.
| Ia | = | 1 | 1 | 1 | × | I₀ |
| Ib | = | 1 | a² | a | × | I₁ |
| Ic | = | 1 | a | a² | × | I₂ |
where a = 1∠120° = −0.5 + j0.866
What to notice
When only positive sequence is present, phases are balanced at 120° separation. Add negative sequence and watch the symmetry break.
| Fault | Symmetry | +Seq | −Seq | 0Seq | Severity | Ground |
|---|---|---|---|---|---|---|
| Three-Phase | Balanced | Yes | No | No | Equipment duty basis | No |
| SLG | Unbalanced | Yes | Yes | Yes | System dependent | Yes |
| Line-to-Line | Unbalanced | Yes | Yes | No | ~87% of 3φ (Z₁≈Z₂) | No |
| DLG | Unbalanced | Yes | Yes | Yes | High | Yes |
Solid arrows: phase-to-ground voltages at the fault point (from the solver). Dashed: pre-fault 1.0 pu reference. In an ungrounded ground fault the neutral shifts to the faulted phase and the healthy phases rise to the line-to-line value √3 ≈ 1.73 pu, 60° apart.
Fault Behavior
Select a fault type to see how it changes phase currents and sequence components.
Always present
No source
Needs ground path
No Fault
Only positive-sequence network is active. System is balanced.
Solidly Grounded
Zero sequence tends to show up only when the system gives it somewhere to go.
Click & drag phasor tips to change magnitude and angle (fixed 1.5 pu axis scale)
Interactive Mode
Drag the phasors above, or use the sidebar controls. Both update in real-time.
Challenge 1: Ground Fault Detection
Configure the system so a single line-to-ground fault produces detectable zero-sequence current (I₀ > 0.1 pu) while keeping maximum phase current moderate.
Challenge 2: Current Limiting
Set up a system where three-phase fault current stays below 5 pu. Think about source strength and fault location.
Challenge 3: Ungrounded Awareness
Demonstrate why an ungrounded system fails to produce zero-sequence current during a ground fault. Set grounding to ungrounded and apply an SLG fault.
Challenge 4: Maximum Asymmetry
Create the most asymmetric fault condition possible: maximize the ratio of negative-sequence to positive-sequence current.
Goal: Ground Fault Detection
- Fault type must be SLG or DLG
- Zero-sequence current I₀ must be > 0.1 pu
- Maximum phase current must be < 10 pu
Why Symmetrical Components Matter
Power systems are designed for balanced three-phase operation. But faults are unbalanced events. Analyzing them directly in three phases is painful—the math couples together and the physics gets tangled.
Symmetrical components (Fortescue, 1918) decompose any unbalanced three-phase set into three balanced sets:
- Positive sequence: Equal magnitude, 120° apart, ABC rotation. Normal operating condition.
- Negative sequence: Equal magnitude, 120° apart, ACB rotation. Appears during unbalanced faults.
- Zero sequence: Equal magnitude, in phase. Related to ground current flow.
How They Simplify Faults
- Three-phase: Only positive sequence. Balanced.
- Line-to-line: Positive and negative in parallel at fault point.
- SLG: All three networks in series. I₁ = I₂ = I₀ when a zero-sequence return path exists and the model includes it.
- DLG: Positive in series with negative ∥ zero. Current divides between negative- and zero-sequence branches based on their impedances.
- Fault impedance Zf: enters as a series phase impedance for 3φ and LL faults, and as 3Zf in the zero-sequence (ground-return) branch for SLG and DLG. A DLG fault with no ground path degenerates to a line-to-line fault with Zf still in series.
Common Mistakes
Reality: Zero sequence is involved in ground faults, but only if there is a path for it. Ungrounded systems have ground faults without zero-sequence current. Idealized zero-sequence current is zero if capacitive charging is ignored.
Reality: Three-phase faults are commonly used for equipment-duty calculations. However, the maximum fault current depends on transformer connection, grounding, location, and sequence impedances. DLG can exceed 3φ in certain configurations.
Reality: It exists whenever the system is unbalanced—including normal small imbalances. High levels cause heating in machines.
What to Notice
- Watch phasor shape change as you switch fault types
- SLG and DLG have zero-sequence; LL does not
- Switch to “ungrounded” and watch I₀ disappear—even during a ground fault
- Three-phase fault is purely positive sequence
- Try the interactive phasors in Scenario Lab