Phase Academy Interactive Power Systems Lab
Service & Feeder Conductor Sizing
NEC 2023
Educational / design-assist tool — NEC 2023 only. This calculator is accurate within a declared scope (insulated Cu/Al feeders and services on Table 310.16). It is not a claim of universal NEC compliance and is not a substitute for the adopted NEC text, AHJ interpretation, manufacturer equipment markings, or professional engineering judgment. Out-of-scope cases are flagged.
Sizing Path
Correction & Adjustment Factors
Ambient correction and conductor-count adjustment multiply together, then the terminal column caps the usable ampacity.
Ambient Correction
CCC Adjustment
Combined Factor
Terminal Cap
Usable Ampacity by Conductor Size
Usable (capped) Selected Next Up Crit. A (terminal) Crit. B (corrected)
Bars show usable ampacity = min(terminal-column, ambient- & count-adjusted). Hover a bar for the underlying numbers.
Headroom Analysis
Educational Disclaimer: For learning and design assistance only. Not a substitute for the adopted NEC text, AHJ interpretation, manufacturer markings, or professional engineering judgment.
Sizing Results
Overcurrent Protection (240.4 / 240.6)
OCPD sizing is provided for reference and is separate from conductor ampacity. Next-size-up (240.4(B)) never makes an undersized conductor acceptable for the actual load.
Next Larger Conductor
Ampacity Adjustment Flow
How the insulation-column ampacity is corrected/adjusted and then capped by the terminal column.
Capacity Utilization
Step-by-Step Calculation Trace
Every number has a reason and a cited NEC reference. Both sizing criteria are shown separately; the governing one is highlighted.
Assumptions & Scope
    Design Challenge Mode
    The system describes a scenario. You pick the conductor. The same engine that runs the calculator grades your work — there are no hard-coded answer keys.

    Select a challenge above

    Choose a challenge to see the scenario description and constraints.
    NEC 2023 Reference Panel
    Paraphrased NEC logic. Always consult the adopted code text for exact requirements.
    Service vs. Feeder Comparison
    AspectFeederService
    DefinitionAll conductors between the service equipment (or other power source) and the final branch-circuit overcurrent deviceFrom the service point to the service disconnecting means
    NEC ArticleArt. 215Art. 230
    Overcurrent protectionProtected by upstream OCPDGenerally no supply-side OCPD
    Ampacity basis215.2 / 215.3230.42
    Minimum sizePer ampacity calculationOverhead: 230.23(B); Underground: 230.31(B)
    Dwelling allowance310.12 (if it carries the whole dwelling load)310.12 (one-family & unit services)

    Why This Matters

    Undersized conductors overheat. Oversized conductors waste money and complicate installation. Conductor sizing sits at the intersection of safety, economics, and code compliance — getting it right means the circuit works safely under worst-case conditions, not just on a mild Tuesday.

    Service conductors carry additional weight because they generally lack upstream overcurrent protection. A feeder has a breaker watching its back; a service conductor has to fend for itself.

    The Two Sizing Criteria

    A compliant conductor must satisfy both of these — the smallest size that passes both criteria is selected (and it must additionally be protectable by the overcurrent device the load requires, per 240.4):

    • Criterion A — terminal column (110.14(C)). The ampacity from the permitted terminal column (usually 60°C or 75°C) must be at least the noncontinuous load plus 125% of the continuous load.
    • Criterion B — correction/adjustment (310.15). The insulation-column ampacity, multiplied by the ambient correction (Table 310.15(B)(1)(1)) and the conductor-count adjustment (Table 310.15(C)(1)), must be at least the total connected load.

    The 90°C column may be used for the correction/adjustment math even when the terminals are only 75°C — but the final usable ampacity is still capped at the terminal column.

    Common Mistakes

    • Ignoring terminal temperature limits. A 90°C wire on 75°C terminals uses the 75°C column for the terminal check. The insulation sets the ceiling; the terminal sets the operating limit.
    • Forgetting the 125% continuous factor. If a load runs 3+ hours, the terminal check is sized at 125% (unless the assembly is listed for 100%).
    • Wrong material column. Reading copper values for aluminum (or vice-versa) is silent and expensive.
    • Overlooking ambient correction. A 46°C rooftop is not a 30°C basement.
    • Bundling without adjusting. More than 3 current-carrying conductors triggers Table 310.15(C)(1).
    • Assuming the neutral never counts. Per 310.15(E), a wye neutral on a majority-nonlinear load is a current-carrying conductor.

    The Third Gate — The Conductor Must Be Protectable

    Passing both ampacity criteria is not enough. The overcurrent device the load actually requires must also be a device that is permitted to protect the chosen conductor under 240.4. The classic trap: a 25 A noncontinuous load needs a 25 A device, and #12 Cu is 25 A at 75°C — but 240.4(D) caps #12 Cu protection at 20 A, so #12 is not a lawful answer. This calculator applies that check as a third selection gate, so the headline size is always one you can actually protect.

    Reading the Status Badge

    The badge grades the margin of the governing criterion, using thresholds chosen by this tool — they are editorial, not code:

    • PASS — at least 10% margin over the governing requirement.
    • TIGHT — the conductor complies but has less than 10% margin. A code-minimum conductor is fully compliant; TIGHT is a design comment, not a violation.
    • FAIL — no size satisfies the criteria (see the warnings).

    What This Tool Deliberately Does Not Do

    • Voltage drop (210.19(A) / 215.2(A) Informational Notes) is not evaluated. It is a performance recommendation, not a requirement, but it frequently governs long runs.
    • Article 220 load calculation is upstream of this tool — you supply the calculated load.
    • Rooftop sunlit-raceway ambient (310.15(B)(2)) is not added automatically; include it in the ambient you enter.
    • 310.15(C)(1) exceptions (raceway nipples ≤ 600 mm / 24 in., certain spaced cables) are not applied — the tool stays conservative.
    • Grounded (neutral) conductor sizing per 220.61, equipment grounding conductors (250.122), parallel sets (310.10(G)), and derating for conduit fill are outside this scope.

    Overcurrent Protection & the “Next Size Up” Rule

    OCPD sizing is implemented here (240.6(A) standard ratings, 240.4(D) small-conductor limits, and the 240.4(B) next-standard-size allowance up to 800 A). Important: 240.4(B) may let you round the overcurrent device up to the next standard size — it never lets an undersized conductor carry a load its ampacity cannot support. Small conductors (#14–#10) are additionally capped by 240.4(D) regardless of calculated ampacity.

    Conductor Material

    Copper and aluminum are not interchangeable. Aluminum needs larger sizes, different terminations, and careful torque specs. Note that 4/0 aluminum is not a general 200 A Table 310.16 conductor at 75°C (its 75°C ampacity is 180 A); it is only a 200 A answer under the dwelling allowance of NEC 310.12. A general 200 A aluminum service needs 250 kcmil.

    Educational Disclaimer: For learning and design assistance only. Not a substitute for the adopted NEC text, AHJ interpretation, manufacturer markings, or professional engineering judgment. Always verify results independently.