Phase Academy Interactive Power Systems Lab

Power Sequence Simulator

Generator · ATS · Emergency Power
Normal utility service. All loads served from utility source.
Active Source
Utility
ATS Position
Normal (N)
Generator
Standby
Emergency Source
N/A
System State
NORMAL
Elapsed Time
0s
Loads Served
All
Warnings
None
📊 Load Status
Life Safety100%
Critical100%
Equipment100%
Non-Essential100%
⏱ Timing Breakdown — How Long Are Loads Without Power?

Based on your current slider settings, here's how the timeline breaks down. Total blackout = detection (1s) + start/crank + warmup + ATS transfer. All times are in simulated seconds (the simulator runs at approximately 10× real time).

Total Blackout
29
seconds without power
Cranking
10
seconds to start
Warmup
15
seconds to stable V/F
ATS Transfer
3
seconds to switch
Detect 1s
Crank 10s
Warmup 15s
Transfer 3s
On Gen
🔁 Quick Sequence Overview
Utility OK Utility Fail Gen Start Gen Warmup ATS Transfer Loads on Gen Utility Returns Retransfer Cooldown
💡 Did You Know?

The 10-second benchmark: NEC Article 700 (700.12) requires emergency power to be available within the time required for the application, not exceeding 10 seconds. Under NFPA 110, generator systems serving such loads are typically classified Level 1, Type 10 (“Level” is NFPA 110 terminology, not NEC). This simulator uses the 10-second figure as a learning benchmark only; full code compliance depends on many factors beyond timing.

Try it: Toggle utility power off in the sidebar and watch the full sequence unfold. Then check the Timing Breakdown panel above to see how your settings compare to the 10-second benchmark.

📋 Sequence Timeline

Each event in the power transfer sequence, with timing and delays made visible. Times are simulated seconds; the simulator runs at 10× real time.

T+0s
System normal — utility supplying all loads
⚡ One-Line Power Flow Diagram

Active sources and power paths highlighted in real time. Click any icon for details. Simplified single-ATS model: NEC requires emergency-system transfer equipment to supply only emergency loads — legally required standby and optional loads use separate transfer switches. This simulator collapses them into one ATS for clarity.

🔌 Power Source Summary
Utility
Available
Generator
Standby
ATS
Normal
Emergency Loads
Served
🧠 Control Logic State Machine

The decision states the ATS controller moves through. Think of it as the system's brain.

Utility Present?
YES
Start Command
OFF
Generator Ready?
ATS Transfer
NORMAL
Retransfer
Cooldown
📖 Control Decisions Explained

The ATS controller continuously monitors utility voltage and frequency. When utility power is present and acceptable, no action is needed. When utility fails, the controller sends a start command to the generator and waits for the generator to reach acceptable voltage and frequency before transferring.

🔬 Scenario Lab

Click any card to auto-configure settings and watch the scenario play out. Each scenario adjusts the sidebar controls and runs automatically.

Power Outage → Generator Transfer

Utility fails. Generator starts, warms up, ATS transfers. The core emergency sequence.

What to watch: Total blackout time, each state transition in order

Generator Fails to Start

Utility fails but the generator won't crank. Emergency loads stay dark. A worst-case scenario.

What to watch: State machine stops at FAILED_START — no transfer possible

Bad Voltage / Frequency

Generator starts and runs, but output is unstable. The ATS correctly refuses to transfer.

What to watch: Generator reaches BAD_VF state — ATS protects loads from bad power

Full Cycle (Outage → Recovery)

Complete sequence: utility fails, generator takes over, utility returns, ATS retransfers, generator cools down.

What to watch: All states from start to finish, including retransfer delay and full cooldown

Overloaded Generator

Generator capacity below total demand. Non-essential loads are shed to protect critical systems.

What to watch: Load bars show priority shedding — life safety stays at 100% with priority ON

Reset to Normal

Restore all defaults (sliders, toggles) and return to normal utility service.

🔧 Build Your Own Scenario

Use the sidebar controls to set up any combination of conditions, then hit Simulate Outage. Try these challenges:

  • Set start/crank to 30s — watch how long loads wait in darkness
  • Enable "Bad V/F" — see the ATS refuse to transfer even though the generator is running
  • Enable "Failed Start" — understand what happens when backup fails the backup
  • Set generator capacity to 50% and disable load priority — see proportional load reduction
  • Set retransfer delay to 120s — learn why patience prevents double-transfer failures

Why This Matters

When utility power fails, the difference between a managed transition and chaos is a sequence of timed, logical steps. Emergency power systems don't just "turn on" — they follow a precise state machine that balances speed against safety.

Every hospital, data center, and high-rise depends on this sequence working correctly. Understanding it isn't optional — it's foundational.
Scope note: This simulator illustrates concepts. It is not a control sequence validator and does not determine NEC/NFPA compliance. Full compliance depends on equipment listing, source type, transfer equipment, wiring separation, capacity, testing/maintenance, occupancy requirements, manufacturer settings, and AHJ interpretation.

The Core Sequence

  1. Normal Operation — Utility feeds all loads through the ATS (Normal position)
  2. Utility Failure Detected — ATS senses loss of acceptable voltage/frequency (small detection delay)
  3. Start Signal — ATS sends start command to generator
  4. Generator Cranking / Starting — Engine cranks and attempts to start
  5. Warmup Period — Generator runs but must reach acceptable V/F before transfer
  6. ATS Transfer — ATS switches from Normal to Emergency position
  7. Emergency Operation — Loads served from generator
  8. Utility Returns — ATS senses utility restoration, starts retransfer timer
  9. Retransfer — ATS switches back to Normal (utility) position
  10. Cooldown — Generator runs unloaded to cool down before shutdown
Timing model used here: Total blackout = detection delay (1s, fixed) + start/crank time + warmup + ATS transfer. This is a simplified educational model — real installations may include additional delays (engine ramp, synchronizing, controller settling, breaker operation).
NEC Article 700 context: Emergency power (or emergency lighting) must be available within the applicable time limit, not exceeding 10 seconds. The alternate source may be a generator, UPS, battery/unit equipment, fuel cell, or other listed source depending on system design and adopted code edition. Generator sets requiring more than 10 seconds to assume load may need an auxiliary source (e.g., UPS or battery) to bridge emergency loads until the generator is ready. Related but distinct: legally required standby systems (NEC Article 701) must be available within 60 seconds, and optional standby systems (Article 702) have no code-mandated time limit — each is a separate system with its own transfer equipment.

ATS Logic & Timing

The Automatic Transfer Switch is the decision-maker. It monitors both sources and only transfers when conditions are met:

  • Transfer to Emergency: Only when generator voltage AND frequency are within acceptable limits
  • Retransfer to Normal: Only after utility has been stable for the retransfer delay period — adjustable by controller/facility requirements; use manufacturer settings and AHJ/project requirements
  • Break-before-make: The ATS disconnects from one source before connecting to the other — a brief interruption is expected during the switch
  • Transition types: This simulator models an open-transition (break-before-make) ATS. Closed-transition (make-before-break) and delayed-transition types also exist. The transfer-time slider represents total programmed transfer timing — the mechanical switch operation itself takes only a fraction of a second

Common Mistakes

  • Assuming instant transfer — There are real, physical delays at every step
  • Forgetting warmup — A running generator is not the same as a ready generator
  • Ignoring retransfer delay — Transferring back too quickly risks double-outage if utility flickers
  • Skipping cooldown — Cooldown is manufacturer/controller dependent and is most relevant to engine/turbocharger thermal management
  • Not planning for failed start — If the generator does not start, you need a backup plan (UPS, redundant gen)

What to Notice

  • The total blackout time is detection delay + start/crank + warmup + ATS transfer — often 15–30 seconds with default settings
  • Load priority determines which loads come back first (life safety, then critical, then equipment, then non-essential)
  • Load shedding protects the generator from overload by dropping non-essential loads
  • The retransfer delay prevents "bouncing" — if utility flickers back briefly then fails again

Load Shedding & Priority

When a generator can't handle the full load, the system must decide what stays powered. This simulator uses an example share split:

  • Life Safety: 20% (egress and emergency lighting, exit signs, fire alarm) — never shed when priority is ON
  • Critical: 30% (operating rooms, patient-care areas, critical process loads)
  • Equipment: 30% (critical HVAC, elevators)
  • Non-Essential: 20% (general lighting, convenience outlets) — shed first

Fire pumps are intentionally not listed: they take power through a dedicated path under NEC Article 695 / NFPA 20 and are not part of building load-shed schemes.

Load shedding is not a failure — it is a feature. It means the system is protecting itself and prioritizing what matters. Real installations use programmable load shed schemes and may use frequency-based or breaker-trip-based shedding. Real systems never shed life-safety loads — the priority-OFF proportional mode in this simulator exists for comparison only.

Quiz: Test Your Understanding

1. The utility fails and the generator starts, but the ATS does not transfer. What is the most likely reason?

2. After utility returns, why doesn't the ATS transfer back immediately?

3. The generator starts and the ATS transfers, but emergency loads are still partially off. Why?

4. What is the correct sequence after utility failure?

5. Why does the generator run unloaded after loads transfer back to utility?

6. In this simulator (detection delay 1s), the generator takes 7s to crank, 8s to warm up, and 2s for ATS transfer. Total blackout time?

7. During load shedding with priority ON, which loads should be dropped FIRST?

8. The utility flickers back on for 5 seconds then fails again. What prevents the ATS from transferring back and forth rapidly?

Configuration Challenge

Read the scenario requirement below, configure the sidebar sliders to match, then click Check Configuration to see if you got it right.

Challenge: Meet this simulator's 10-second emergency transfer timing benchmark. Configure the system so total blackout time is 10 seconds or less. Minimums: start/crank 3s, warmup 5s, ATS transfer 1s.
Educational Disclaimer: This is a conceptual simulator designed to teach the general principles of emergency power sequencing. It is not control sequence validation software and should not be used for system design, commissioning, or safety-critical decisions. Actual ATS and generator control sequences vary by manufacturer, application, and local codes. Always consult equipment documentation and qualified engineers for real installations. Code references reflect NEC 2023 and NFPA 110 (2022); verify against the edition adopted in your jurisdiction.