⚠ Leading Power Factor Warning
⚡ Harmonics Caution
Adding capacitor banks to nonlinear loads (VFDs, welders) risks resonance. This simulator does not model harmonic resonance. Real installations require harmonic analysis and may need detuned reactors or active filters.
💡 Insight
Adjust the controls on the left to see how power factor correction affects your electrical system. Start by changing the capacitor bank slider.
Before Correction
After Correction
⚠ Over-correction detected!
⚡ Harmonics risk
This load type contains nonlinear elements. Standard capacitor banks can amplify harmonic currents. This simulator does not model harmonic resonance. Real installations require harmonic analysis.
Before
After
🏭 Factory Floor
480V 3-phase, 500 kW motor-heavy load, PF 0.72 lagging. High penalty risk.
🏢 Office Building
480V 3-phase, 200 kW mixed commercial, PF 0.88 lagging. Moderate improvement possible.
🔨 Welding Shop
240V single-phase, 80 kW welders, PF 0.60 lagging. Severe PF, harmonics concern.
🖥 Data Center
480V 3-phase, 1000 kW VFD-heavy, PF 0.92 lagging. Already decent; fine-tune correction.
⚠ Over-Correction Demo
See what happens when you add too many capacitors. 480V 3-phase, 150 kW, PF 0.75 lag + 200 kVAR cap.
↺ Leading Initial Load
480V 3-phase, 100 kW, PF 0.80 leading. Demonstrates auto-correct refusal for leading loads.
The Power Triangle
Every AC electrical load has three types of power:
- Real Power (P) — measured in kW. This is the useful work: turning shafts, producing heat, running computers.
- Reactive Power (Q) — measured in kVAR. This energy shuttles back and forth to sustain magnetic fields in motors, transformers, and ballasts. It does no useful work but is required by inductive loads.
- Apparent Power (S) — measured in kVA. This is what the utility must deliver. It is the vector sum.
Power Factor
Power factor is the ratio of real power to apparent power. A PF of 1.0 means all supplied energy does useful work. A PF of 0.70 means the utility must deliver ~43% more current than needed for the real load, increasing losses and costs.
Lagging PF (most common) is caused by inductive loads — motors, transformers, solenoids. Leading PF can be caused by over-correction with capacitors or lightly loaded synchronous motors.
Power Factor Correction
Capacitors supply reactive power locally, reducing the reactive demand from the utility. The capacitor kVAR needed:
This reduces line current, transformer loading, and I²R losses. Many utilities charge penalties for PF below 0.90 or 0.85.
Worked Example
Common Mistakes
- Over-correcting to unity (PF = 1.0): Dangerous at light load. Target 0.95 to leave margin.
- Ignoring harmonics: Capacitors + VFDs or welders can create resonance. Use detuned reactors.
- Placing all capacitors at the main bus: Better to distribute near large motors.
- Not accounting for load variation: Switched capacitor banks adapt; fixed banks can over-correct at light load.
- Forgetting leading PF penalties: Some utilities penalize leading PF too.
Test Your Knowledge
See if you can answer these based on what you just learned.