CF = 2^((measured − reference) / 10) and corrected = raw × CF. A reading taken warm reads low and is scaled up. The reference defaults to 20 °C, matching the ANSI/NETA conversion table for non-rotating apparatus. Correction behaviour varies by insulation system, so the method used is stored with every reading. Do not use this 20 °C method for rotating machinery — IEEE 43 corrects motor and generator windings to 40 °C.
>1000, <5, OL for overrange, or a G suffix for gigohms. Points that were not tested must be marked N/A with a reason — a blank required point reads as INCOMPLETE, never PASS.| Test Point | Applicable | Raw / Qualifier | CF | Corrected | Min (MΩ) | Result | Notes / N/A reason | Actions |
|---|
What this record is for
Insulation resistance testing is one of the most common measurements in NETA acceptance and maintenance testing. On a panelboard, switchboard, MCC or switchgear line-up it answers a narrow but important question: is the insulation between each energized conductor and ground, and between conductors, still doing its job?
The measurement itself takes a minute. Making it defensible takes the rest of this form — the instrument and its calibration, the criteria you judged against and where they came from, the temperature the equipment was at, what was disconnected, and the as-found and as-left condition of the gear.
Before test voltage is applied
An insulation resistance tester applies 250–15,000 V DC. Establishing an electrically safe work condition first is not optional.
- Determine all sources feeding the equipment, including back-feeds, control power and UPS or generator sources.
- Open the disconnecting means for each source and visually verify open where the design allows.
- Apply lockout/tagout per the employer's program (OSHA 1910.147 and 1910.333, NFPA 70E Article 120).
- Verify absence of voltage on every phase conductor and the neutral with an adequately rated tester, proving the tester on a known source before and after the check (NFPA 70E 120.6).
- Apply grounds where induced or stored voltage is possible.
- Disconnect what the test would destroy — surge protective devices, electronic trip units and metering, potential transformers, control circuits, VFDs and anything with solid-state components. This is also where NEC 110.3(B) bites: the manufacturer's instructions govern the test method and any voltage limit.
Test voltage and minimum values
Test voltage is selected from the equipment's rated voltage class, not from the actual operating voltage of the moment. The values below are the widely published ANSI/NETA Table 100.1 recommendations, which this tool uses as its representative criteria. Verify them against the edition of the standard adopted for your project, and remember that the manufacturer's published minimum always takes precedence when it is higher.
| Equipment voltage rating | Minimum DC test voltage | Recommended minimum insulation resistance |
|---|---|---|
| 250 V | 500 V | 25 MΩ |
| 600 V | 1,000 V | 100 MΩ |
| 1,000 V | 1,000 V | 100 MΩ |
| 2,500 V | 1,000 V | 500 MΩ |
| 5,000 V | 2,500 V | 1,000 MΩ |
| 8,000 V | 2,500 V | 2,000 MΩ |
| 15,000 V | 2,500 V | 5,000 MΩ |
| 25,000 V | 5,000 V | 20,000 MΩ |
| 34,500 V and above | 15,000 V | 100,000 MΩ |
The standard test duration is one minute. This tool defaults to 60 s and records the duration with every reading, because a 30-second reading and a 10-minute reading on the same insulation are different measurements.
Why temperature correction matters
Insulation resistance falls as temperature rises — roughly halving for each 10 °C increase. A panel tested at 35 °C in August and the same panel tested at 15 °C in February will produce readings that differ by a factor of about four with no change whatsoever in the insulation.
That is why every reading in this record is corrected to a common reference temperature before it is compared against the acceptance criterion or against a previous test:
CF = 2^((measured − reference) / 10) · corrected = raw × CFAt a 20 °C reference: 10 °C → 0.50 | 20 °C → 1.00 | 30 °C → 2.00 | 40 °C → 4.00
Use the right reference. 20 °C is the reference for the NETA conversion table covering non-rotating apparatus — panels, switchgear, buses, cables. Rotating machinery is a different discipline: IEEE 43 corrects motor and generator windings to 40 °C, and mixing the two conventions will make good insulation look bad or bad insulation look acceptable.
Humidity and dew point. Surface leakage across dirty or damp insulation can dominate the reading. If the equipment temperature is at or near the dew point, moisture is condensing on the insulating surfaces and the measurement reflects that film rather than the insulation itself. This tool flags readings taken within 2 °C of the recorded dew point.
Reading the results
- PASS — every required point is recorded and its corrected value is at or above the investigate threshold (the minimum multiplied by the investigate factor, 2× by default).
- INVESTIGATE — the corrected value clears the minimum but sits below the investigate threshold. It is not a failure, but it is a trend worth watching and worth a note in the report.
- FAIL — the corrected value is below the minimum. Investigate before energizing: the usual culprits are moisture, contamination, a load or SPD left connected, or genuinely degraded insulation.
- INCOMPLETE — a required point is blank, or a point was marked N/A without a reason, or measurements exist but no criterion was resolved to judge them against. A panel in this state can never report PASS.
Trending beats absolute values. A single reading proves very little beyond a gross failure. The value of a record like this one is comparison — panel against identical panel, and this year against last year, both corrected to the same reference temperature.
Codes and standards referenced
| Reference | What it covers |
|---|---|
| ANSI/NETA ATS | Acceptance Testing Specifications — inspection and test procedures for newly installed equipment, including insulation resistance test values in Table 100.1. |
| ANSI/NETA MTS | Maintenance Testing Specifications — the equivalent procedures and criteria for existing equipment being maintained. |
| ANSI/NETA ETT | Standard for certification of electrical testing technicians — the basis for the technician qualification recorded on this form. |
| IEEE 43 | Recommended practice for testing insulation resistance of rotating machinery — 40 °C reference, polarization index. Not applicable to the panels covered here. |
| NFPA 70E 120 | Establishing an electrically safe work condition, lockout/tagout, and verification of absence of voltage. |
| NFPA 70E 130 | Work involving electrical hazards — risk assessment, approach boundaries, PPE. |
| NEC 110.3(B) | Listed and labeled equipment must be installed and used in accordance with the instructions included in the listing or labeling — including test limits. |
| NEC 110.26 | Working space about electrical equipment — the space you need to safely perform this test. |
| NEC 230.95(C) | Ground-fault protection equipment must be performance tested when first installed on site — a companion field test frequently performed on the same visit. |
| OSHA 1910.147 / .333 | Control of hazardous energy, and selection and use of work practices for electrical safety. |