Light blue = connected nameplate. Navy = demand after factors. Amber = categories where demand exceeds connected (e.g., motor 125% adder).
Step-by-Step Calculation Trace
Each category's demand path, then feeder totals, continuous sizing, and current. Values in kVA unless noted; motor steps show amperes.
Method & Assumptions
Demand by Category
| Category | Ref (paraphrased) | Connected | Demand | DF | Δ vs conn. |
|---|
Δ: green = reduction (savings); amber = increase/adder (demand > connected).
Sizing & OCPD
🎯 Design Challenge
Estimate the sizing parameters for the loads you entered, then check against the tool's calculation. This is a learning aid — not a substitute for a stamped calculation.
How Scoring Works
Demand within ±5% and sizing current within ±10% earn full marks. The ampere-rating answer should equal the minimum standard rating ≥ the sizing current (240.6(A)). Real conductor/OCPD selection also depends on ampacity, terminations, corrections, listing, and the next-size rule — not scored here.
NEC References 2023
Paraphrased section pointers for the selected edition. Not code text — consult the adopted NEC and AHJ.
Edition Notes
Engine Self-Test
Deterministic unit tests run against the pure calculation engine (same engine the UI uses). Results also print to the browser console.
What This Tool Does — and Does Not Do
This tool estimates feeder/panelboard demand load (Article 220 standard method, with Article 430 for motors) and a sizing basis that adds the continuous-load factor. It is a calculation aid and teaching tool.
Corrected Concepts
- Lighting is not "10 kVA/50%". General-lighting demand factors are occupancy-specific (dwelling, hospital, hotel, warehouse, or "all others" at 100%).
- Receptacle 10 kVA/50% applies to non-dwelling receptacle loads only, not to lighting or dwelling receptacles.
- 75% fixed-appliance factor is dwelling-only, needs 4+ qualifying fastened-in-place appliances, and excludes ranges, dryers, space heating, and A/C.
- Kitchen demand is never less than the two largest pieces of equipment.
- Motors increase the load. 125% of the largest FLC is an adder, not a reduction; use table FLC, not nameplate.
- Noncoincident heating vs cooling: include only the larger.
- A/C & heat-pump compressors are motors (Art. 440). On a feeder that also carries other motors they belong in the 430.24 largest-motor determination — this tool does not do that and warns instead.
Common Mistakes This Tool Guards Against
- Applying a universal lighting reduction.
- Using dwelling appliance factors on commercial feeders.
- Treating nameplate kVA as motor FLC without a warning.
- Double-counting heating and cooling.
- Trusting feeder sizing on mixed HVAC + motor feeders without an Art. 440 check.
- Calling a design "compliant" from bus utilization alone.
- Reporting demand > connected as green "savings".