Phase Academy Motor Branch-Circuit Calculator
verified
Study tool — NEC Article 430 single-motor conductor + branch SC/GF OCPD educator. Local NEC adoption varies by jurisdiction: verify the enforced edition, equipment markings, engineering judgment, and AHJ interpretation. Not a substitute for licensed design or plan review.
⚠ Data for this NEC edition is not fully verified in this tool. Values are provisional and must not be treated as code-compliant. Confirm against the published edition.
Scope: One single motor only. Computes branch-circuit conductor ampacity (430.22), branch short-circuit / ground-fault OCPD (430.52), separate overload (430.32, nameplate), and equipment grounding conductor (250.122). Not included: feeder conductors/OCPD, multiple-motor circuits, VFD/adjustable-speed drive circuits, disconnecting means, controllers, SCCR / available fault current / interrupting ratings, voltage drop, and local amendments.
Table FLC
A
NEC Table 430.248 / 430.250
Required Ampacity
A
430.22
Selected Conductor
Table 310.16
Max Branch OCPD
A
Table 430.52

Result

Live Utilization Gauges

These gauges update in real time as you adjust inputs on the left.

Conductor Use
OCPD Headroom
OCPD : Conductor
Motors run large by design
Input Power
kW (est.)

Motor Branch-Circuit One-Line

Each element updates with your inputs.

Why This Matters

Motor circuits follow different rules because motors behave differently. During startup, a motor draws several times its running current for a few seconds. If the branch OCPD were sized to protect the conductor at 125% — the rule for ordinary loads — every start could be a nuisance trip.

The NEC splits motor protection into separate devices with separate jobs:

Branch OCPD (430.52)

Short-circuit & ground-fault only

Sized large (from table FLC) to let the motor start. Protects conductors from faults, not from overload.

Overload (430.32)

Running overload only

Sized close to nameplate FLA. A separate device. Trips on sustained over-current.

Educational Disclaimer: This tool is for learning and reference support only. It is not a substitute for engineering judgment, licensed review, plan examination, or AHJ interpretation, and it does not perform complete motor installation design.

Motor Starting Current Simulation

Illustrative startup vs running behavior — why the branch OCPD can't be small.

Instantaneous Current
0.0 A
Phase
Stopped

Illustrative inrush (~6× FLC for a typical Design B motor) decaying over ~1–3 s. Actual inrush depends on the motor code letter, load, and drive. The OCPD must ride through starting without tripping.

Current & Ampacity Comparison

Side-by-side view of the ampere values in the branch calculation.

Time–Current Coordination (illustrative)

Motor starting (purple) vs branch OCPD (red) vs overload (yellow). Schematic only — not a substitute for a coordination study.

Conductor Size Comparison (Copper vs Aluminum)

For your required ampacity, at the selected insulation/termination settings.

Table 430.52(C)(1) Multiplier Matrix

Max branch OCPD as a percent of FLC per motor row / OCPD type. Your selection is highlighted. Instantaneous-trip values are settings.

FLC vs. Horsepower (At Your Voltage)

How table FLC scales across HP at your voltage. Your motor is highlighted.

Educational Disclaimer: Charts are illustrative. Verify all values against the applicable NEC edition.

Step-by-Step Calculation Trace

Every value below is produced by the pure calculation engine (window.MotorCalc).

Assumptions

    Exclusions (not evaluated by this tool)

    • Feeder conductors and feeder OCPD (430.24 / 430.62).
    • Multiple motors / combination loads on one circuit.
    • VFD / adjustable-speed-drive branch circuits (Article 430 Part X / 409).
    • Disconnecting means (430.109) and controller (430.83) ratings.
    • Available fault current, SCCR, and OCPD interrupting rating (110.9 / 110.10).
    • Voltage drop, and local / AHJ amendments.
    Educational Disclaimer: Trace is derived from paraphrased NEC logic. Consult the applicable NEC edition directly.

    Sizing Results

    Interpretation Notes

    Overload vs. Short-Circuit / Ground-Fault Protection

    Separate device (430.32)

    Overload Protection

    A separate overload device (heaters, electronic, or integral). Sized from motor nameplate FLA — typically 115% or 125%, or up to 140%/130% under 430.32(C).

    Branch OCPD (430.52)

    Short-Circuit & Ground-Fault Protection

    The branch OCPD. Sized large from table FLC to ride through starting. Protects conductors from faults.

    Conductor vs. OCPD Comparison

    Educational Disclaimer: Always verify your design against the adopted NEC edition and local amendments. This tool does not confirm code compliance.

    ◆ Design Challenge Mode

    Score: 0 / 0

    A motor scenario is generated and graded against the same engine used everywhere else in this tool.

    Your Challenge History

    Track your progress across scenarios.

    No challenges submitted yet. Pick an answer above and click Submit to start.
    Educational Disclaimer: Design Challenge is a learning exercise. Real-world motor circuit design requires review of all applicable conditions, coordination, and AHJ interpretation.

    How Motor Circuits Are Different

    For most loads, the NEC sizes the OCPD to protect the conductor and the conductor to carry the load. Motors break this pattern: inrush current is several times running current during startup. Sizing the branch OCPD at 125% of FLC could trip on every start.

    The NEC solves this by splitting protection into layers:

    • Branch-circuit short-circuit and ground-fault protection (430.52) — sized large from table FLC.
    • Motor overload protection (430.32) — a separate device sized from nameplate FLA.

    FLC → Conductor & OCPD Sizing Path

    What to Notice

    Common Mistakes

    • Using nameplate FLA for conductor / branch OCPD. Those come from Tables 430.248 / 430.250 (table FLC). Nameplate FLA is for overload — and for non-continuous-duty conductor sizing under 430.22(E).
    • Applying Article 240 conductor-protection rules. Motor branch OCPDs can be much larger than conductor ampacity — by design.
    • Forgetting the separate overload device. The branch OCPD does not protect against overload.
    • Mixing copper and aluminum ampacities. They are not interchangeable per size.
    • Ignoring the termination temperature limit. You may derate from the 90°C column, but the final ampacity is capped at the 60°C or 75°C termination column (110.14(C)).
    • Not using the next standard size. 430.52(C)(1) Exception 1 permits the next higher standard size (240.6) when the calculated value isn't standard — except instantaneous-trip breakers, which are settings.

    ◉ Interactive Quiz

    Score: 0 / 0

    Test your understanding. Each question has one correct answer.

    Educational Disclaimer: Quiz questions are teaching tools. They simplify real-world scenarios. Always consult the actual NEC and your AHJ.

    NEC Reference Panel

    Article and table references. NEC language is paraphrased for education — always consult the actual code text.

    Quick Article Index (Article 430)

    • 430.6(A) — Use table FLC (not nameplate) for conductor / branch OCPD sizing
    • 430.22 — Branch-circuit conductor sizing (single motor)
    • 430.22(E) — Duty-cycle conductor sizing (non-continuous)
    • 430.32 — Overload protection (nameplate FLA)
    • 430.52 — Branch SC / GF protection
    • Table 430.248 — Single-phase motor FLC
    • Table 430.250 — Three-phase motor FLC
    • Table 430.52(C)(1) — Max OCPD percentages
    • Table 310.16 / 310.15(B)(1) / 310.15(C)(1) — Ampacity, ambient, adjustment
    • 240.6 / 250.122 — Standard sizes / EGC
    Educational Disclaimer: References are paraphrased. Consult NFPA 70 (NEC) for authoritative text.

    ✓ Built-in Self-Test

    Runs the pure calculation engine against known NEC cases plus a DOM smoke test. Also runnable headless via tests/motor-calc.spec.mjs and callable as window.runSelfTests().

    Note: These tests validate the tool's internal math and runtime, not the correctness of a real installation.