Phase Academy Interactive Power Systems Lab

General Lighting & Receptacle Calculator

Educational NEC 2017–2026
AHJ Notice: NEC edition adoption varies by jurisdiction. Verify which code cycle your local Authority Having Jurisdiction (AHJ) has adopted, plus any local amendments, before applying any calculation to a real project. Table values in this tool must be verified against the legally adopted NEC edition (NFPA 70 / NFPA Link).
Lighting (connected)
VA
Receptacles (connected)
VA
Dedicated (connected)
VA
Connected / Calculated Load
VA
Branch-Circuit Sizing Load
VA
Min. Calculated Circuits
Connected Load Breakdown
Connected VA
Calculated-Minimum Utilization
sizing load vs. calculated-minimum capacity
This is informational headroom for the auto-calculated minimum, not a code pass/fail. PASS / CAUTION / FAIL is reserved for the Circuit Designer, where you commit to a fixed circuit count.
Load Comparison Bars
Lighting
Receptacles
Connected
Sizing load
General-Purpose Rating Comparison

🔌 Dedicated / Non-General Loads

Add specific equipment, appliance, motor, sign, show-window, or EVSE loads. Each row is treated as its own branch-circuit requirement and is never distributed across the general lighting or receptacle circuits.

Description VA or W Unit Qty Voltage Category Cont. Rating Circuits
"VA or W": values entered in watts are treated as VA at power factor = 1.0 (an educational simplification). Adjust to VA if the equipment power factor is known. Suggested rating is the smallest standard rating that keeps the (sizing) load at or below the circuit rating; confirm against equipment nameplate and applicable article.
Σ Dedicated Load Summary
🔧 Design Your Circuit Arrangement

Add circuits to build a fixed arrangement for the general-purpose branch-circuit sizing load (lighting + receptacles). Because you commit to a specific number of circuits here, PASS / CAUTION / FAIL is meaningful. Dedicated loads are sized separately on the Dedicated Loads tab.

"Copper and aluminum are not interchangeable just because optimism is free."

YOUR CIRCUITS
Add circuits below to start designing.
Click × to remove
Total Capacity
load vs capacity
Circuit Count
0
circuits in your design
Calculated minimum (general-purpose):
Headroom
VA spare capacity
Per-Circuit Load Distribution
Idealized split: the general-purpose sizing load is distributed across circuits in proportion to each circuit’s capacity. A real panel schedule assigns specific outlets to specific circuits, so actual per-circuit loading will differ — this shows whether the arrangement has enough total capacity, not how to balance it.

"The code path matters. The answer did not appear by magic."

📐 Step-by-Step Calculation Trace
StepDescriptionCalculationResult
Enter inputs to generate trace.
Assumptions Applied by This Tool
    ? Assumptions Requiring Confirmation

    Confirm each against NFPA Link / licensed NEC text / your AHJ before any design use.

      § NEC Reference Panel

      Paraphrased logic generated from the selected edition — consult the NEC for binding language.

      Code Logic Summary
      Edition Notes

      Why This Matters

      Branch-circuit loading determines how many circuits a space needs and how large they must be. Every panel schedule, wire pull, and breaker selection depends on these numbers.

      • Under-sized circuits trip repeatedly — nuisance outages.
      • Over-sized circuits waste panel space and cost.
      • The NEC unit-load method provides a standardized baseline without knowing every fixture in advance.

      Common Mistakes (that this tool now guards against)

      • 180 VA per receptacle instead of per yoke: A duplex on one yoke is one 180 VA unit, not two.
      • Adding dwelling receptacles separately: Dwelling and hotel/motel guest-room general-use receptacles are already in the unit lighting load (220.14(J)).
      • Applying 125% to everything: The continuous multiplier applies only to loads that are actually continuous, and only for conductor/OCPD sizing.
      • Double-counting 125% under NEC 2020/2023: Those tables carry a note saying the 210.20(A) continuous multiplier is already included in the unit loads. Re-applying it inflates the load. This tool suppresses it for table-based non-dwelling lighting and says so in the trace.
      • Using 2017 unit loads under a 2020+ citation: The 2020 cycle reconstructed the table for LED lighting — offices went 3.5 → 1.3 VA/ft², but armories/auditoriums went up 1.0 → 1.7. Using the old number is not always conservative.
      • Entering a custom VA/ft² below the table value: The unit load is a minimum — “shall not be less than.” A measured lighting design lower than the table does not lower the calculated load.
      • Treating 220.14(K) as optional: For banks and offices it is a “shall” provision. The receptacle load is the greater of 180 VA/yoke or 1 VA/ft².
      • Applying the receptacle demand factor to the 1 VA/ft² value: The 220.44/220.47 demand covers loads calculated per 220.14(H) and (I) only — not the 220.14(K)(2) area-based value.
      • General-use receptacles on 277 V: Not permitted (210.6). This tool blocks it.
      • General-use receptacles on a 30 A circuit: Not permitted unless a listed 30 A equipment receptacle is used.
      • Forgetting the dwelling required circuits: 210.11(C) mandates two small-appliance circuits, a laundry circuit, and a bathroom circuit regardless of the general-lighting math.
      • Spreading dedicated loads across general circuits: Dedicated loads get their own circuits.

      What Changes With the Edition

      💡 Key Concepts

      Connected vs. Calculated vs. Sizing

      Connected = raw unit loads. Calculated = NEC unit-method load. Sizing = calculated plus the 125% adder on continuous loads for conductors/OCPD.

      Receptacle Load

      180 VA per yoke/strap (220.14(I)). Not about what is plugged in — about what could be. For offices/banks, compare against 1 VA/ft².

      Branch-Circuit Loading

      Total VA on a circuit vs. rated capacity. Voltage × ampere rating = circuit VA. Exceed it → more circuits needed.

      Continuous vs Non-Continuous

      Continuous = max current for 3+ hours. Conductor/OCPD sizing uses 125% of the continuous portion. Note: a load-calculation article does not necessarily itself apply 125%.

      🏢 Occupancy Concept Cards

      "The NEC is trying to help, even when it feels personally inconvenient."

      Engineering Self-Test

      Runs deterministic unit tests against the calculation engine (the same pure functions used by the UI and by the Node test file). Results also print to the browser console. Append ?selftest=1 to auto-run on load.