⚠ Scope — what this tool checks
It interprets the marked MCA/MOCP from listed HVAC/refrigeration equipment to check only (1) branch-circuit conductor ampacity against MCA and (2) selection of a standard OCPD not exceeding MOCP, under the stated assumptions. It does not verify SCCR/AFC, interrupting rating, available fault current, disconnect location, working clearances, GFCI requirements, conductor fill, voltage drop, grounding/bonding, wet-location suitability of the conductor insulation, manufacturer installation instructions, equipment listing, or AHJ amendments. Passing here is not a determination of full installation compliance.
📌 AHJ & Assumptions
AHJ adoption: NEC edition adoption varies by jurisdiction — verify the code cycle adopted by your local AHJ before applying any sizing decision. 2026 is the current NEC edition but is not implemented in this tool. Assumptions: unless you change the adjustment fields, results assume no ampacity adjustment (30°C ambient, ≤3 current-carrying conductors, no rooftop adder), a non-NM wiring method, and terminal temperature ratings verified per 110.14(C). NM-B is capped at the 60°C column when selected. Blank ambient or conductor-count fields are treated as errors, never silently defaulted.
Translate MCA (Minimum Circuit Ampacity) and MOCP (Maximum Overcurrent Protection) from an HVAC nameplate into conductor and OCPD selections. The inputs on the left update every tab live — change a value and watch the trace, charts, and visualizer respond.
MCA — minimum ampacity for branch-circuit conductors. Already includes the 125% factor on the largest motor.
MOCP — the largest breaker or fuse permitted. A ceiling, not a target.
💡 Insight
The MCA sizes the wire; the MOCP caps the breaker or fuse. They are independent checks — a design can pass one and fail the other. Use the Calculation Trace tab to see each step with its code basis.
Enter MCA and MOCP to generate a trace.
- Conductor ampacities reference NEC Table 310.16 (≤3 current-carrying conductors baseline).
- Ambient defaults to 30°C; ambient correction uses a table-based correction factor (NEC ambient-correction table for 30°C-based ampacities) when you change ambient or add a rooftop adder.
- More than 3 current-carrying conductors applies the 310.15(C)(1) adjustment factor.
- Final ampacity is capped at the terminal-temperature column (110.14(C)); NM-B is capped at the 60°C column (334.80).
- Type XHHW-2 conductors are exempt from the rooftop sunlight temperature adder (all supported editions).
- MOCP is treated as a maximum device rating — not a recommendation to use that exact size, and never a value to exceed.
- No voltage drop, conductor fill, SCCR/AFC, wet-location suitability, or grounding/bonding analysis is included.
MCA
—
Find ≥ MCA
—
MOCP
—
Standard ≤ MOCP
—
Adjust inputs in the sidebar to generate notes.
- Panel & Breaker: sized in proportion to your selected OCPD. Turns red if it exceeds MOCP.
- Conductors: stroke width scales with ampacity. Red animation = undersized for the load.
- Equipment block: shows the nameplate values driving the calculation.
- OCPD margin stat: the MOCP−MCA spread is a device-rating margin that lets the OCPD ride through compressor inrush — it is not the inrush current itself (locked-rotor current is typically 4–8× the rated-load amps and is handled by the device's time–current characteristic).
🎯 Design Challenge
Click a difficulty to begin
A nameplate scenario will appear here.
- Conductor: +5 if you pick the optimum minimum size; +3 if oversized but legal; 0 if undersized.
- OCPD: +5 if exactly the max permitted standard size; +3 if smaller and reasonable (≥ MCA); +1 if below MCA — legal for grading here but flagged for nuisance-trip risk on motor inrush; 0 if over MOCP.
- Difficulty multiplier: Easy ×1, Medium ×1.5, Hard ×2.
- Streaks: consecutive perfect scores light a flame for bonus motivation.
The MCA/MOCP interpretation workflow is broadly similar across editions, but the editions are not identical. The 2017 edition numbers the allowable-ampacity table 310.15(B)(16); the 2020 edition reorganized Article 310 and renumbered it Table 310.16, which the 2023 edition retains. The 2023 edition also updates 240.6(A) so that 10A is a standard breaker/fuse rating (in 2017/2020 a 10A device is a fuse-only rating), and reduces the rooftop clearance threshold from 7/8 in. (23 mm) to 3/4 in. (19 mm). 2026 is the current NEC edition but is not implemented in this tool; use only if/when a full 2026 data set is added. Always size against the specific adopted edition and verify ampacity values in that code book.
Why This Matters
- Safety: Undersized conductors overheat. An OCPD above the marked MOCP defeats the manufacturer's listed protection coordination (overload/locked-rotor), violating 440.22 and 110.3(B).
- Compliance: Inspectors check MCA/MOCP against installed wire and breaker — a common violation.
- Efficiency: The nameplate gives the answer. Reading it correctly beats manual motor calcs.
- Coordination: The manufacturer sized MOCP for motor starting plus protection. Don't break it.
Common Mistakes
- Using MOCP as the conductor sizing basis. (MOCP is for the breaker; size wire to MCA.)
- Exceeding MOCP because the breaker trips on startup. (The startup problem lies elsewhere.)
- Ignoring terminal temperature ratings. 90°C wire on 75°C terminals = 75°C ampacity.
- Multiplying MCA by 1.25 again. (It already includes the 125% motor-circuit factor of 440.32/440.33.)
- Treating Cu and Al ampacities as interchangeable.
- Going up to the next standard breaker when MOCP is already a standard size.
- Installing a breaker where the nameplate says “Maximum Fuse Size” — device-type markings are binding (110.3(B)).
What to Notice
- MCA and MOCP are required markings, not suggestions.
- The MCA–MOCP gap is a device-rating margin that lets the OCPD ride through motor inrush — it is not the inrush current itself.
- Multi-compressor RTUs have surprisingly high MCA — that's the sum of loads + 125% on the largest.
- If required markings are missing, verify the listing/manufacturer data and apply the applicable NEC article. Do not assume this tool can size unmarked equipment.
Nameplate (Article 440)
- Read MCA from nameplate
- Find conductor ≥ MCA in the ampacity table
- Read MOCP from nameplate
- Select OCPD ≤ MOCP (and the permitted device type)
Manual (Article 430)
- Look up motor FLAs
- Apply 125% to the largest
- Sum all motor + non-motor loads
- Look up OCPD percentages
- Size conductors & devices separately