Phase Academy Interactive Power Systems Lab

Harmonics & Waveform Distortion Lab

Educational Power Quality
Selected Harmonic THD (orders 3–13)
0.0%
Distortion Severity (app heuristic)
Clean
Neutral Current (% of fund. phase)
0%
Harmonic Heating Index (HHI)
1.0
「∿」 Composite Waveform
📊 Harmonic Spectrum
Waveform Interpretation

Adjust the harmonic sliders or pick a preset to explore how harmonics distort a clean sine wave.

✓ Clean Fundamental
⚠ Distorted Composite
∿ Layered Harmonic Construction
Each harmonic drawn individually so you can see how they stack.
📊 Harmonic Magnitude by Order
📋 Harmonic Breakdown
💡 What This Means

The harmonic spectrum shows the magnitude of each frequency component relative to the fundamental.

⚡ Triplen Harmonics & Neutral Current

In a balanced 3-phase system, most harmonics cancel in the neutral. Triplen harmonics (3rd, 9th, etc.) do not cancel. They sum as RMS: Ineutral = 3 × √(Σ Itriplen²).

Assumption: this formula applies to balanced phases carrying identical harmonic spectra. Any unbalance puts all orders — including the fundamental — into the neutral, and 5th/7th cancellation also relies on that balance.

Neutral status

Toggle three-phase mode and add triplen harmonics to see the effect.

🌡 Transformer Impact

Harmonics cause additional eddy-current and hysteresis losses in transformer cores and windings. K-rated transformers are designed to withstand the thermal effects of harmonic currents (they do not filter harmonics).

HHI
1.0
K-Factor
1.0
Suggested K-Rating
K-1
⚠ System Stress Indicators

Scenario Lab

Click a scenario to load its harmonic profile, then explore the effects across all views.

🔍 Scenario Analysis

Select a scenario above to see its analysis.

✓ Design Validation Checker
Evaluate the current harmonic profile against IEEE 519 reference limits, equipment sizing, and neutral conductor considerations. Select an Analysis Type in the sidebar to enable IEEE 519 checks.
📋 Recommendations

Adjust harmonic sliders to see recommendations.

⚡ Equipment Sizing Summary

Equipment sizing guidance will appear here.

What Are Harmonics?

Harmonics are integer multiples of a fundamental frequency. In a 60 Hz system, the 3rd harmonic is 180 Hz, the 5th is 300 Hz, and so on. A perfectly clean power system has only the fundamental—a pure sine wave. Real loads add harmonics to the mix.

“A sine wave is a beautiful thing—right up until nonlinear loads get involved.”

Fundamental vs. Harmonic Frequencies

The fundamental is the intended frequency—50 or 60 Hz depending on your grid. Every harmonic rides on top of it. The 5th harmonic at 300 Hz completes five full cycles for every one cycle of the fundamental.

Waveform Distortion & THD

Total Harmonic Distortion (THD) quantifies how much a waveform deviates from a pure sine. It's the ratio of all harmonic content to the fundamental, expressed as a percentage. This tool computes THD from selected orders 3–13 only. A full-spectrum meter would include all measurable orders.

“THD is the system's way of saying your waveform has been through some things.”

Nonlinear Loads

Linear loads (resistors, incandescent bulbs) draw current proportional to voltage—no harmonics added. Nonlinear loads (VFDs, rectifiers, LED drivers, switching power supplies) draw current in pulses or chunks, creating harmonic frequencies.

Common harmonic producers: variable-frequency drives, UPS systems, computers, LED drivers, arc furnaces, welders.

Triplen Harmonics & Neutral Danger

Triplen harmonics are the 3rd, 9th, 15th, etc.—odd multiples of three. In a balanced three-phase system, most harmonics cancel in the neutral conductor. Triplens don't cancel; they sum as RMS. The neutral current from triplens is 3 × √(Σ Itriplen²), not a simple arithmetic sum. This assumes balanced phases with identical harmonic spectra—unbalance adds every order, fundamental included, to the neutral.

“Triplen harmonics do not politely cancel. They show up in the neutral uninvited, and they bring friends.”

Transformer Heating & K-Factor

Harmonics cause extra heating in transformer windings and cores. Eddy-current losses increase roughly with the square of frequency, meaning a 5th harmonic causes ~25× the eddy-current loss per unit current of the fundamental. K-rated transformers are designed to withstand the thermal effects of harmonic currents—they do not filter or remove harmonics.

The Harmonic Heating Index (HHI) = 1 + Σ(h² × rh²). K-Factor = loadPU² × HHI. Standard K ratings: 1, 4, 9, 13, 20, 30, 40, 50.

Power Quality Impact

Distorted waveforms can cause: nuisance tripping of breakers, overheating of conductors and equipment, interference with sensitive electronics, resonance with power-factor correction capacitors, and increased energy losses throughout the distribution system.

Why This Matters

Modern buildings are packed with nonlinear loads. Data centers, LED lighting retrofits, and VFD-controlled HVAC all contribute harmonics. Understanding harmonics is no longer optional for electrical professionals—it's fundamental to designing reliable systems.

Common Mistakes

  • Assuming the neutral is always low-current in three-phase systems
  • Sizing transformers only for kVA without considering harmonic content
  • Ignoring THD until equipment starts failing
  • Confusing power factor correction with harmonic filtering
  • Thinking K-rated transformers filter harmonics (they only tolerate them)

What to Notice

  • Watch how the waveform flattens or sharpens as you add harmonics
  • See how the 3rd harmonic alone creates a distinctly “chunky” waveform
  • Notice that THD rises quickly once several harmonics are present
  • Observe how triplen harmonics light up the neutral current indicator

Test Your Knowledge

See if you can answer these based on what you just learned.

1. Which harmonic type is most dangerous for neutral conductors?

2. A waveform with 25% THD means:

3. K-rated transformers:

Educational Disclaimer: This is a conceptual visualization tool for learning purposes. It is not a field measurement instrument. Real-world harmonic analysis requires calibrated power quality meters and professional expertise. THD shown here includes only selected orders (3rd–13th); a real meter measures all orders present. Severity bands and resonance-risk indicators are app-specific screening heuristics, not standard limits. Waveform shapes and values shown are illustrative approximations.