Grounding System Designer
Select a component from the palette, then click / tap the canvas to place it (auto-deselects after placing). Drag placed components to reposition. Click ports (colored dots on edges) to start a wire, then click another port to connect. Click a component to select it, then press Delete to remove. Wires route with right-angle bends. Loading an example also sets the sidebar method / system so Validate Design grades against the matching context.
Normal Current Path
Source → Phase conductor → Load → Neutral conductor → Source. Current returns via the neutral (grounded conductor).
Fault Current Path
No fault present. Select a fault location to visualize the fault return path.
Bond Location Status
Neutral Current Status
Fault Return Integrity
Likely Symptoms
Code / Concept Notes
Event Log
Phase (Hot)
Carries load current from source to utilization equipment.
Neutral (Grounded)
Returns normal load current to the source. Grounded at the service or SDS origin.
EGC (Equipment Grounding)
Safety path for fault current. Low impedance return to trip overcurrent device.
Key Differences
Select different configurations to see how correct and incorrect installations compare.
1. Normal Operation
Standard utility service, solidly grounded, proper N-G bond. All conductors functioning correctly.
2. Ground Fault at Load
Phase-to-ground fault at equipment. See how fault current returns via EGC to trip the breaker.
3. Missing N-G Bond
What happens when the main bonding jumper is removed? Fault current has no low-impedance return path.
4. Open Neutral
Neutral conductor is broken. Line-to-neutral voltages become unstable; neutral current may seek unintended metallic return paths.
5. HRG System
High-resistance grounded system. First ground fault is alarmed, not tripped. Limits fault current.
6. SDS Transformer
Separately derived system with system bonding jumper at the SDS source. GEC connection to the grounding electrode system required; a separate ground rod is not automatically required.
7. Generator (Switched Neutral / SDS)
Standby generator with switched (4-pole) neutral transfer. Generator is a separately derived system; system bonding jumper at generator.
8. Double N-G Bond
Bonded at both source and sub-panel. Normal neutral current splits onto EGC -- a code violation.
Grounding vs Bonding -- What's the Difference?
- Grounding = connection to earth (typically through a grounding electrode system). Establishes a voltage reference and stabilizes the system against voltage swings.
- Bonding = electrically connecting metallic parts together to maintain continuity. Creates the metallic effective ground-fault current path used to clear faults.
- Key insight: Earth alone is generally not relied on as a fault-return path. The intentionally bonded metallic path is what clears faults; earth grounding provides voltage reference, lightning / surge reference, and a common potential.
The N-G Bond (Main Bonding Jumper)
- Connects the grounded conductor (neutral) to the equipment grounding conductor at the source.
- Required at service entrance (NEC 250.24) or at separately derived system origin (NEC 250.30).
- Only ONE point of connection per system. Multiple bonds cause neutral current on EGC.
Separately Derived Systems
- A system with no direct electrical connection to the supply conductors of another system (NEC 250.30).
- Requires a system bonding jumper at the SDS source (or first disconnecting means as permitted) and a GEC connection to the grounding electrode system. This does NOT automatically mean driving a separate ground rod.
- The grounding electrode system can include building steel, metallic underground water pipe, concrete-encased electrode, or a ground ring, in addition to (or instead of) rods.
- Examples: isolation transformers; generators with switched neutral (4-pole transfer); some UPS configurations.
Why an Earth-Only Return Path Is Typically Inadequate
- Earth resistance varies widely with soil and electrode design (often several ohms to tens of ohms or more). A metallic EGC is usually a small fraction of an ohm.
- By Ohm's law, current divides among parallel paths in inverse proportion to their impedance. Most of the current will take the lowest-impedance path.
- Illustrative example: 120 V across a 25 Ω earth path ≈ 4.8 A. At that current, a typical 15 A or 20 A thermal-magnetic breaker may not operate on overcurrent alone in a useful time. Actual fault current depends on system voltage, source impedance, conductor impedance, electrode resistance, soil conditions, and bonding.
- That is why the intentionally bonded metallic path (the effective ground-fault current path, NEC 250.4(A)(5)) is what is relied on to clear faults -- not earth grounding alone.