Design Dashboard
EV charging is where continuous-load treatment stops being theoretical.
💡 Insight
Adjust the controls to see how EVSE sizing propagates from branch circuit to service.
Results
Branch circuit · feeder aggregation · service entrance
Amps on the EVSE voltage basis. Aggregate is the sum of each EVSE at 125%, before any load-management cap.
Dashed outline is service capacity. Bars turn red when demand exceeds it.
Relative index, not dollars. The window centers on the selected conductor; sizes with no published index show as N/A.
Red dashed line marks the 3% branch-circuit recommendation from the NEC Informational Note. Voltage drop is advisory, not a code pass/fail.
How ambient correction, conductor grouping, and the terminal-temperature cap reduce usable ampacity for the selected conductor.
Calculation Trace
The code path matters. The answer did not appear by magic.
📋 Assumptions
| Step | Description | Calculation | Result |
|---|
Design Challenge
Design it. The system will tell you if you got it right.
Learn Mode
Article 625 in practice
Why EVSE sizing is different
Electric vehicle supply equipment runs at its maximum rating for hours at a time. The NEC classifies any load that operates for three hours or more as a continuous load, and Article 625 states outright that EV charging loads are continuous. That single sentence drives everything else on this page.
- A single Level 2 charger adds 40–50A of continuous load — comparable to adding a second electric range that never turns off.
- The 125% margin exists for thermal headroom in conductor insulation and equipment terminations, not for future capacity.
- Multi-charger installations routinely overwhelm services that looked adequate on paper.
The sizing hierarchy
- Branch circuit: One dedicated circuit per EVSE (625.40). Size conductor and OCPD at 125% of the EVSE rated current.
- Feeder: Sum the connected EVSE loads at 125%, add any non-EV load, then size the feeder OCPD and conductors (215.2/215.3). The NEC provides no generic quantity-based diversity factor for EVSE.
- Service: Add the EV demand to the rest of the calculated load (Article 220) and compare with the service rating. Service conductors follow 230.42(A) — 125% of continuous plus 100% of non-continuous.
Ampacity is not one number
Table 310.16 gives a base ampacity in three insulation columns. Two corrections and one cap stand between that number and what you may actually use:
- Ambient correction (310.15(B)): Applied in the insulation column. A 75°C conductor at 40°C ambient keeps only 88% of its rating.
- Grouping adjustment (310.15(C)): More than three current-carrying conductors in a raceway — 80% at 4–6, 70% at 7–9, 50% at 10–20.
- Terminal temperature cap (110.14(C)): 90°C wire terminating on 75°C lugs is limited to the 75°C column. The 90°C column is useful for derating, not for final ampacity.
Common mistakes
- Sizing at nameplate: A 48A EVSE on a 50A breaker with 8 AWG copper fails 210.19(A), 210.20(A), and 625.41. It needs 60A and 6 AWG.
- Inventing diversity: "They won't all charge at once" is not a code provision. Without a listed load-management system there is no reduction.
- Ignoring the service: The breaker fits; the service does not. Check both.
- Mixing materials carelessly: Aluminum needs a larger conductor for the same ampacity and drops about 64% more voltage per circular mil.
- Forgetting the terminal cap: Selecting from the 90°C column without checking 110.14(C).
- Skipping voltage drop on long runs: A 200 ft run at 40A on 6 AWG copper is already past 3%.
| Level | Supply | Typical Current | Power | Typical Use |
|---|---|---|---|---|
| Level 1 | 120V 1φ | 12–16A | 1.4–1.9 kW | Overnight, cord-and-plug |
| Level 2 | 208–240V 1φ | 16–80A | 3.3–19.2 kW | Home, workplace, fleet |
| DC Fast | 480V 3φ input | 60–400A+ | 50–350+ kW | Highway, depot |
DC fast charging equipment is sized here on its AC input rating — the DC output side is internal to the listed equipment.
NEC References & Code Logic
Educational paraphrase — verify against your adopted edition
Reference Panel
| Section | What it requires (paraphrased) |
|---|
- Continuous load (Article 100, 210.19(A), 210.20(A), 215.2(A)(1), 215.3, 625.41): EVSE is a continuous load; conductors and OCPD at ≥125% of rated current.
- Standard OCPD ratings (240.6(A)): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400…
- Conductor protection (240.4): OCPD may not exceed conductor ampacity, except where 240.4(B) permits the next standard size up (≤800A, ampacity does not correspond to a standard rating, not a multi-outlet receptacle circuit).
- Small conductors (240.4(D)): Cu 14/12/10 AWG capped at 15/20/30A; Al 12/10 AWG capped at 15/25A.
- Ampacity (Table 310.16): 60/75/90°C columns, copper and aluminum.
- Ambient correction (310.15(B)) and grouping adjustment (310.15(C)), applied in the insulation column.
- Terminal temperature (110.14(C)): final usable ampacity capped at the terminal column.
- Equipment grounding conductor (250.122): minimum EGC from the OCPD rating.
- Feeder / service (215.2, 215.3, 220.40, 230.42(A)): aggregate EV load plus other load, sized on the continuous basis.
- Load management (625.42): where a listed system limits the maximum EV load, the feeder/service may be sized to that controlled maximum.
- Voltage drop (Informational Notes to 210.19(A) and 215.2(A)): 3% branch / 5% total recommendation — advisory, not enforceable.
runSelfTests(), or by loading this page with #selftest.