Phase Academy Interactive Power Systems Lab

EGC Sizing Calculator

NEC 250.122 · Table 250.122
AHJ NoticeNEC edition adoption varies by jurisdiction. Verify the code cycle adopted by your local Authority Having Jurisdiction.
Minimum EGC
Your EGC
cmil Ratio
Verdict

Conductor Area Comparison

Visual

Bars show circular-mil area (NEC Chapter 9, Table 8). The minimum threshold is marked on your EGC bar.

Grounding Path Diagram

EGC vs GEC

Distinction

EGC — Equipment Grounding

  • Effective ground-fault current return path
  • Base size from Table 250.122 by OCPD, then adjusted
  • Runs with the circuit conductors
  • Helps the OCPD clear a fault

GEC — Grounding Electrode

  • Connects system to the grounding electrode
  • Sized per Table 250.66
  • At service / separately derived system
  • Normally not a load-current conductor

Why This Matters

Foundation

The EGC is part of the effective ground-fault current path. During a fault it must carry enough current to operate the OCPD quickly — before someone is hurt or equipment is damaged. An undersized or discontinuous EGC may not clear the fault fast enough, or at all.

The base wire-type EGC size is selected from Table 250.122 by the OCPD rating — not the load and not the phase-conductor size alone — then adjusted for applicable rules such as proportional upsizing, parallel installations, multiple circuits, motor circuits, and the effective ground-fault current path requirement.

Step-by-Step Calculation Trace

Deterministic

Every value below is derived from your inputs. Nothing is hidden.

Assumptions & Limits

Transparency
  • Base wire-type EGC from NEC Table 250.122 using the smallest row ≥ the OCPD rating.
  • Circular-mil values are exact (NEC Chapter 9, Table 8). The 250.122(B) ratio is not rounded before selecting a standard size, and the selection ladder is restricted to real Chapter 9 Table 8 conductor sizes.
  • Exact mathematical sizing is conservative; AHJ / qualified-person interpretations may differ where rounding is considered. The 250.122(B) Exception (2020+) permits a qualified person to size for an effective ground-fault current path per 250.4(A)(5)/(B)(4) instead.
  • The 250.122(A) “need not exceed the circuit conductors” cap is applied only when EGC and phase materials match; otherwise it is left to engineering / AHJ review.
  • This tool does not verify circuit-conductor ampacity. It never checks the phase conductors against 240.4 / 310.16. A capped or “passing” result says nothing about whether the circuit conductors themselves are legally sized.
  • Wire-type EGCs only; raceway/armor continuity, terminations, and fault-current adequacy are not evaluated.

Sizing Result

Minimum EGC

Comparison Table

ParameterValue

Adequacy Gauge

Visual
EGC Adequacy

OCPD-to-EGC Mapping

Table 250.122

The row used for your OCPD is highlighted.

OCPD not exceeding (A)CopperAluminum / Cu-clad Al

Challenges use the same computeEGC() engine as the main calculator (NEC 2023 method, exact circular-mil sizing). Your score updates live from the current field values.

Challenge 01

Size the EGC

A 100 A breaker protects a feeder with 1 AWG copper phase conductors. What is the minimum copper wire-type EGC?

Challenge 02

Upsized Phase Conductor

A 60 A circuit requires minimum 6 AWG copper phase conductors, but you install 4 AWG for voltage drop. Using exact circular-mil sizing, what minimum copper wire-type EGC should you use?

Challenge 03

Parallel Feeders (Separate Raceways)

A 400 A feeder uses 2 parallel sets of 3/0 AWG copper in separate raceways. How many wire-type EGCs do you need, and what size (copper)?

Challenge 04

EGC or GEC?

Match the scenario to the correct conductor type:

“Bonds motor frame back to panel”
“Connects panel to ground rod”
“Sized from Table 250.122 by OCPD”
Challenge 05 · Full Design

Design a Complete EGC Installation

200 A feeder, aluminum phase conductors, 3 parallel sets in separate raceways, phase conductors upsized from 4/0 AWG to 250 kcmil for voltage drop. Size the wire-type EGC for each raceway.

Challenge Score

0 / 5

NEC Reference Panel

NEC 2023

Article 250 — Grounding and Bonding

Article 250 governs grounding and bonding. Wire-type EGC sizing is in 250.122 / Table 250.122.

SectionTopicParaphrased Logic

Edition Notes

What Is an EGC?

An equipment grounding conductor connects non-current-carrying metal parts of equipment back to the system grounding point, forming part of the effective ground-fault current path. During normal operation it is normally not a load-current conductor. During a ground fault it must carry enough current to help operate the OCPD.

It is a safety path that exists for fault and abnormal conditions.

How EGC Sizing Actually Works

The base wire-type EGC size is selected from Table 250.122 by the OCPD rating. That base is then adjusted for applicable rules — proportional upsizing (250.122(B)), parallel installations (250.122(F)), multiple circuits (250.122(C)), motor circuits (250.122(D)), and the overriding requirement to maintain an effective ground-fault current path (250.4(A)(5)).

Larger OCPD generally means more available fault energy and a larger base EGC — but the OCPD row is the starting point, not the whole story.

Motor Circuits · 250.122(D)

For motor circuits the EGC is sized from Table 250.122 using the rating of the branch-circuit short-circuit and ground-fault protective device (selected per 430.52), which is often much larger than the conductor ampacity would suggest. This tool does not model 430.52 device selection.

Multiple Circuits · 250.122(C)

Where several circuits share one raceway, cable, trench, or cable tray, a single EGC sized for the largest OCPD among them is permitted to serve them all. This is a permissive allowance — it never requires a smaller conductor than 250.122 would otherwise demand.

Upsizing & EGC

250.122(B)

When phase conductors are increased in size (often for voltage drop), a wire-type EGC that is installed must be increased proportionally by circular-mil area. In the 2020 and later editions this does not apply where the increase is only to satisfy the ampacity adjustment/correction factors of 310.15(B)/(C).

Required EGC (cmil) = Base EGC (cmil) × ( Installed Phase cmil ÷ Min Phase cmil )

This tool selects the smallest standard Chapter 9 Table 8 conductor whose area is ≥ the exact required cmil (it does not round the ratio down). Exact sizing is conservative; some AHJs accept documented rounding methods.

Exception (2020+)

A qualified person is permitted to size the EGC to provide an effective ground-fault current path in accordance with 250.4(A)(5)/(B)(4) instead of the strict circular-mil method. This tool always applies the strict circular-mil method.

Parallel Conductors

250.122(F)

Where conductors run in separate raceways or cables, a wire-type EGC is installed in each raceway/cable, each sized per Table 250.122 from the feeder/branch-circuit OCPD — not divided among the sets (250.122(F)(1)(b)).

Where parallel conductors share a single raceway, auxiliary gutter, or cable tray, a single wire-type EGC sized by the OCPD is permitted (250.122(F)(1)(a)). Where a wire EGC is installed in a cable tray it must also meet the minimum in 392.10(B)(1)(c), per 250.122(F)(1)(c). A qualifying metal raceway may itself serve as the EGC under 250.122(F)(1)(d) and 250.118.

Multiconductor cable assemblies each contain their own EGC sized per 250.122 (250.122(F)(2)). Where paralleled multiconductor cables share one raceway, auxiliary gutter, or cable tray, a single combined EGC is permitted per 250.122(F)(2)(c). The 250.122(A) sectioned-EGC allowance also permits an EGC to be run in sections where the wiring method allows.

Common Mistakes

Avoid

Sizing by load current instead of OCPD

A 20 A breaker on a 12 A load still bases the EGC on the 20 A OCPD row.

Confusing EGC with GEC

Different conductors, different tables (250.122 vs 250.66), different purposes.

Wrong material column

Table 250.122 has separate copper and aluminum/Cu-clad-Al columns. Using the wrong one undersizes the EGC.

Rounding the 250.122(B) ratio down

A result just above a standard size (e.g. 16,511 cmil vs 16,510 for 8 AWG) requires the next size up under exact sizing.

Splitting one EGC among separate raceways

Each separate raceway gets its own full-size EGC per 250.122(F).

Reading the 250.122(A) cap as a pass on the circuit conductors

“The EGC need not be larger than the circuit conductors” assumes those conductors are themselves legally sized for the OCPD under 240.4 / 310.16. Capping an EGC to an illegally small phase conductor is not compliance.

EGC vs GEC — Detail

AttributeEGCGEC
Full NameEquipment Grounding ConductorGrounding Electrode Conductor
Sizing TableTable 250.122 (base, then adjusted)Table 250.66
Sized ByOCPD rating (base)Largest ungrounded service/derived conductor
LocationWith circuit conductorsService / separately derived system
PurposeEffective ground-fault current path; helps clear faultsConnects system to earth electrode(s)
CurrentNormally none; carries fault current during ground faultsNormally not a load-current conductor; may carry current under lightning, surge, ground-fault, or abnormal conditions

Equipment grounding conductors are sized by code logic and the effective-path requirement — not by wishful symmetry.

In-File Test Harness

Deterministic

These assertions run against the same computeEGC() engine used by the calculator and challenges. They run on load; use the buttons to re-run. Results also print to the browser console.

#TestExpectedActualResult
!
For Education Only · Verify Against Codes

This tool sizes wire-type EGCs from NEC Table 250.122 and related rules for learning and calculation support only. It does not verify circuit-conductor ampacity (240.4 / 310.16), and does not replace available-fault-current analysis, OCPD time-current coordination, product listing and terminal (temperature) suitability, conductor material restrictions, raceway/armor continuity verification, engineering judgment, plan review, or AHJ interpretation. Always verify against the adopted NEC edition.