💡 Insight
Normal operating conditions. All measurements within expected range.
| Class | Terminal V at 20× | Standard burden | Max sec. current before knee | Primary equivalent |
|---|
| Measured | — |
| Threshold | — |
| Multiple of threshold | — |
| Operating time | — |
| Verdict | — |
runSelfTests(). Running them here does not disturb your settings or quiz progress.⚠ Never open an energized CT secondary
With primary current flowing, an open secondary forces all primary ampere-turns into magnetizing the core. The resulting voltage spikes are lethal and can destroy insulation. Short the secondary with a shorting screw or test switch before breaking the circuit, and treat the work as energized electrical work under NFPA 70E.
What a current transformer does
A CT reproduces a large primary current as a small, standardized secondary current — 5 A or 1 A at rated primary. The nameplate ratio is the turns ratio: a 600:5 CT has 120 secondary turns per primary turn, so it divides by 120.
Metering vs. protection CTs
- Metering (0.15 / 0.3 / 0.6 / 1.2 accuracy class) — specified for ratio and phase-angle accuracy at and around rated current into a standard burden (B-0.1 through B-1.8). Many are built to lose linearity not far above rated current so instruments are protected during faults; the exact knee is design-specific. This simulator models a metering CT as departing from linearity near 4× rated secondary current.
- Protection (C class) — specified to stay within 10% ratio error up to 20× rated secondary current (100 A on a 5 A CT) while delivering the class voltage to its standard burden.
Burden, class voltage, and saturation
Burden is the total impedance the CT drives: relay input, leads (both directions), meters, test switches. To push its secondary current through that burden the CT must develop a terminal voltage V = Iₛₑₓ × Z₋ₕₜₑₖ. The core also has to supply its own winding drop, so the internal excitation voltage is Vₑ = Iₛₑₓ × (R₋ₜ + Z₋ₕₜₑₖ).
Iₛₑₓ × Z₋ₕₜₑₖ below the C-rating at maximum fault current and the CT will reproduce the fault faithfully.- Doubling the burden doubles the required voltage and halves the fault current at which saturation begins.
- Long secondary leads are burden. Sizing conductors up is the usual field fix.
- Burden VA = I² × Z, which is why burden matters far more during a fault than at load.
- Secondary winding resistance is estimated here at 0.0025 Ω per secondary turn — the common rule of thumb for bushing CTs from IEEE C37.110.
- Real saturation is governed by the excitation curve and by DC offset in the fault current; it is progressive, not the hard threshold used in this model.
A saturated CT clips its output, so the fundamental component the relay measures is lower than the true scaled current. Overcurrent elements slow down or fail to pick up, and differential elements can produce false operate current when one CT saturates on a through fault.
Potential transformers
A PT scales system voltage to a standard secondary — typically 120 V line-to-line, or 69.3 V line-to-neutral (120 ÷ √3) for wye-connected sets. A 69 kV : 120 V set has a ratio of 575:1.
Relay elements (IEEE C37.2 device numbers)
- 50 — Instantaneous overcurrent. Operates with no intentional time delay as soon as the measured phase current reaches pickup; real relays add roughly one cycle of operate time.
- 51 — Time overcurrent. Pickup must be held for a time set by an inverse curve. IEEE C37.112 defines
t = TD × (A / (Mᵦ − 1) + B)whereM = I / Iₚₛₘₖₙₛ. Time dial shifts the whole curve; curve shape (moderately, very, extremely inverse) sets how aggressively time collapses as current rises. - 50G / 51G — Ground overcurrent. Fed from residual current (3I₀) or a separate ground CT. Because balanced load cancels in the residual, ground pickups can be set far below load current — that sensitivity is the whole point.
- 87 — Differential. Compares current entering and leaving a zone. Operate = |I₋ + I₊| with correct polarity conventions, restraint = (|I₋| + |I₊|) / 2, and the element operates when operate ≥ pickup + slope × restraint. Through-current cancels; internal faults do not.
Open secondary vs. ungrounded secondary
- Open secondary — the current path is broken while primary current flows. The core drives toward saturation each half cycle and the secondary develops very high peaky voltages. This is a personnel hazard and an insulation hazard. The voltage cannot be predicted from a simple formula, so this simulator reports the condition instead of inventing a number.
- Ungrounded secondary — the loop is closed but has no reference to ground. Capacitive coupling from the primary can float the whole secondary circuit to a dangerous potential. The fix is one, and only one, ground point per secondary circuit; two grounds create a parallel path that corrupts the measurement.
Codes and standards
| Reference | What it governs |
|---|---|
| NEC 250.170 | Instrument transformer circuits: CT and PT secondary circuits shall be grounded where the primary windings connect to circuits of 300 V or more to ground, and on switchboards regardless of voltage (with the code’s stated exceptions). |
| NEC 250.172 | Instrument transformer cases or frames shall be connected to the equipment grounding conductor where accessible to other than qualified persons. |
| NEC 250.174 / 250.176 | Grounding of instrument, meter, and relay cases — below 1000 V and 1000 V or over respectively. |
| NEC 250.178 | Instrument equipment grounding conductor: not smaller than 12 AWG copper or 10 AWG aluminum. |
| NEC 230.95 | Ground-fault protection of equipment on solidly grounded wye services over 150 V to ground and not exceeding 1000 V phase-to-phase, 1000 A and larger: maximum 1200 A setting and maximum 1 s time delay at 3000 A. |
| IEEE C57.13 | Requirements for instrument transformers — accuracy classes, standard burdens, and the C-class definition used throughout this lab. |
| IEEE C57.13.1 / C57.13.3 | Field testing of relaying CTs (ratio, polarity, excitation) and grounding of instrument transformer secondary circuits. |
| IEEE C37.110 | Guide for the application of current transformers used for protective relaying — burden, saturation, and DC offset. |
| IEEE C37.112 | Inverse-time characteristic equations for overcurrent relays — the curve constants used here. |
| IEEE C37.2 | Standard device function numbers (50, 51, 50G, 51G, 87). |
| ANSI/NETA ATS & MTS §7.10 | Acceptance and maintenance testing of instrument transformers: insulation resistance, polarity, ratio, and burden verification against nameplate. |
| NFPA 70E | Work practices for energized work — shorting CT secondaries, test switch use, and PPE for relay and metering work. |
Code text is paraphrased for teaching. Always work from the adopted edition of the code and the manufacturer’s instructions for the actual installation.
Field practice checklist
- Verify the CT nameplate ratio and tap actually in use — multi-ratio CTs are routinely landed on the wrong tap.
- Measure the real burden, including lead resistance both ways, and compare it to the class standard burden.
- Check polarity at every CT with a polarity test per IEEE C57.13.1, not by wire colors.
- Confirm exactly one ground per secondary circuit and that the ground is at the panel, not at the CT.
- Run an excitation (saturation) test on relaying CTs and compare the knee to the maximum expected fault duty.
- Short the secondary before disturbing any CT wiring, and leave shorting devices in place until the circuit is restored.