Phase Academy Interactive Power Systems Lab

Conductor Derating & Adjustment Explorer

Edition-Aware · Self-Tested
Base Ampacity
--
--
After Correction
--
--
After Adjustment
--
--
Final Usable (capped)
--
--
Max OCPD (240.4)
--
--
Factor Waterfall

Ampacity from base through correction, adjustment and the terminal cap.

Code Checks & Margin
Live Factor Breakdown
Interpretation
AHJ Advisory Educational tool. NEC adoption varies by jurisdiction — the edition your local Authority Having Jurisdiction enforces controls. Verify every value against the adopted code text.
Final Ampacity vs. Conductor Count

Terminal cap applied. Dashed line = actual load served.

Show data table
Final Ampacity vs. Ambient Temperature

Banded correction; gaps show ambients with no NEC factor (invalid).

Show data table
Copper vs. Aluminum (final, this size)

Base and final usable (correction × adjustment × terminal cap) for both materials.

Show data table
Insulation Column Comparison (final)

Same conductor, 60/75/90°C columns, each with its own terminal cap applied.

Show data table
Wire Size Progression (final usable)

Final usable ampacity across covered sizes at current conditions. Unavailable sizes are skipped.

Show data table
Correction Factor Bands

Discrete NEC bands (Table 310.15(B)(1)(1)) — step function, not a smooth curve.

Show data table
Adjustment Factor Steps

Conductor count adjustment per Table 310.15(C)(1).

Show data table
Step-by-Step Calculation Trace

Every number below is traceable to a table lookup or a code section.

Assumptions & Not-Evaluated Items
    Factor Summary
    Design Challenge Mode

    Use the sidebar inputs to design a conductor that satisfies every requirement. The system grades your design in real time against the NEC engine.

    Challenges completed: 0 / 0
    Live Design Evaluation

    Active challenge: Select a challenge above

    Select a challenge to begin evaluation.
    Correction vs. Adjustment
    • Correction factor accounts for ambient other than 30°C — a discrete band lookup (Table 310.15(B)(1)(1) in the 2020/2023 editions). Higher ambient → lower factor; a dash means the conductor may not be used at that temperature. The NEC also permits calculating the factor with the equation under 310.15(B); linear interpolation of the table is not a method.
    • Adjustment factor accounts for mutual heating when more than three current-carrying conductors share a raceway/cable (Table 310.15(C)(1)).
    • They multiply. Two 0.8 factors give 0.64, not 0.6.
    What to Notice
    • The 90°C column may be used for correction/adjustment, but the final result is capped at the terminal-temperature column (110.14(C)).
    • Continuous-load rule: size the base/terminal ampacity for noncontinuous load + 125% of continuous load, unless a verified 100%-rated assembly/OCPD exception applies.
    • Going from 3 to 10 current-carrying conductors cuts you to 50% before temperature even enters.
    • Final usable ampacity and the 240.4(D) small-conductor OCPD ceiling are different numbers — don't conflate them.
    Common Mistakes
    • Interpolating the correction-factor table. NEC table bands are discrete. 31°C and 35°C use the same factor. (The permitted alternative is the correction equation, not interpolation.)
    • Assuming ≤100 A defaults to 75°C. Per 110.14(C)(1)(a) the default is the 60°C column unless the equipment/conductors are listed/identified for 75°C.
    • Forgetting the neutral. A 2-wire circuit neutral and a harmonic/nonlinear neutral both count; a balanced wye/MWBC neutral carrying only imbalance does not.
    • Treating final usable ampacity as the allowable OCPD. 240.4(D) can limit the OCPD below the thermal ampacity.
    Terminal Bottleneck (110.14(C))

    Conductor ampacity is limited by the lowest-rated termination. For circuits 100 A or less (or terminals marked for 14 AWG–1 AWG), the default is the 60°C column, unless the equipment and conductors are listed/identified for 75°C.

    Above 100 A (or marked for conductors larger than 1 AWG), use the 75°C column unless otherwise marked. You may derate from the 90°C column, then cap the result at the terminal column value.

    Interactive Quiz

    Click the answer you believe is correct.

    Progress:
    0 / 0
    Educational Disclaimer This tool supports learning; it is not a substitute for engineering judgement, plan review, or AHJ interpretation. Always verify against the applicable NEC edition.
    NEC Reference Panel —

    Rendered from the selected edition's data. References are paraphrased for education; the adopted edition controls.

    Scope & NEC Areas NOT Covered
    Live Self-Tests (acceptance matrix)

    These cases are computed by the live engine on every load and asserted against independently hand-calculated NEC results (verified against NFPA 70-2023 Tables 310.16, 310.17, 310.15(B)(1)(1), 310.15(C)(1)). A red row means the engine regressed.

    Data Provenance

    Ampacity tables and factor tables are transcribed from published NFPA 70-2023 tables (Table 310.16 — conductors in raceway/cable/earth; Table 310.17 — single conductors in free air; Table 310.15(B)(1)(1) — ambient correction; Table 310.15(C)(1) — adjustment). The 2020 edition shares identical values and section numbering for these tables; the edition selector changes only the rooftop clearance threshold (7/8 in. in 2020, 3/4 in. in 2023) and the displayed table designations (Table 310.4(A) vs 310.4(1)). See reviews/conductor-derating-explorer2-review.md in this repository for the verification record.